ΛΕΙΤΟΥΡΓΊΑ
Offset
Περιγραφή
141
Operation State
Outdoor Ambient Tº
142
(Outdoor ambient temperature)
Water Inlet Tº
143
(Water Inlet unit temperature)
Water outlet Tº
144
(Water outlet unit temperature)
145
H-Link Communication State
146
Λογισμικό PCB
147
Λογισμικό LCD
148
Ικανότητα μονάδας
149
Unit Power Consumption
150
Water Outler HP (TwoHP)
Ta1av: Outdoor Unit Ambient Average
151
Temperature
Ta2: Second Ambient Temperature
152
(inst)
Ta2av: Second Ambient Temperature
153
(avg)
154
O2: Water outlet Temp 2 (Two2)
155
O3: Water outlet Temp 3 (Two3)
156
Tg: Gas Temperature (THMg)
157
Tl: Liquid Temperature (THMl)
158
EVI: Indoor expansion valve openning
159
CD: Capacity Data
160
Mixing Valve Opening
161
Απόψυξη
213
PMML0351A rev.4 - 04/2020
Τιμές
0: OFF
1: Cool Demand –OFF
2: Cool Thermo-OFF
3: Cool Thermo-ON
4: Heat Demand-OFF
5: Heat Thermo-OFF
6: Heat Thermo-ON
7: DHW-OFF
8: DHW-ON
9: SWP-OFF
10: SWP-ON
11: Alarm
-80~100
-80~100
-80~100
0: No alarm
1: There is no
communication with
RCS or Yutaki unit
during more than 180
seconds
2: Data initialization
0~100 Μόνο για YUTAKI
S & S Combi
-80~100
-80~100
-80~100
-80~100
-80~100
-80~100
-80~100
0~100
0~100
0: No defrosting
1: Defrosting
Read/Write
VRF
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Read
Availability
RAC
ATW
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O