6. Electrical work
6.2. Field electrical wiring
Outdoor unit model
A12
Ai8
A24
A30
A36
A42
Outdoor unit power supply
Single, 208/230 V, 60 Hz | Single, 208/230 V, 60 Hz | Single, 208/230 V, 60 Hz | Single, 208/230 V, 60 Hz | Single, 208/230 V, 60 Hz | Single, 208/230 V, 60 Hz
Breaker size
*4
15A
415A
25A
30A
30A
30A
Minimum circuit ampacity
13A
138A
18A
25A
25A
26A
Maximum rating of overcurrent protective device
15A
20A
30A
40A
40A
40A
Outdoor unit power supply
2 « Min. AWG 14
2x Min. AWG
14
2x Min. AWG 12
2 «x Min. AWG 10
2x Min. AWG
10
2x Min. AWG 10
> '
Outdoor unit power supply earth
1 x Min. AWG 14
4 1 = Min. AWG
14
4 x= Min. AWG 12
1 x Min. AWG 10
4 x Min. AWG
10
4 = Min. AWG 10
5 < 8
indoor unit-Outdoor unit
*{|
3x AWG 16 (polar)
3 x AWG 16 (polar)
3 x AWG
16 (polar)
3 x AWG 16 (polar)
3 x AWG 16 (polar)
3 x AWG
16 (polar)
=
Indoor unit earth
4
1 x Min. AWG 16
4 1 x Min. AWG
16
4 x Min. AWG 16
1 x Min. AWG 16
4 1 x Min. AWG
16
4 x Min. AWG 16
Remote controfler-Indoor unit
*2| 2 x AWG 22 (Non-polar) | 2 x AWG 22 (Non-polar) | 2 x AWG 22 (Non-polar) | 2 x AWG 22 (Non-polar) | 2 x AWG 22 (Non-polar) | 2 x AWG 22 (Non-polar)
Outdoor unit L1-L2
*3
AC 208/230 V
AC 208/230 V
AC 208/230 V
AC 208/230 V
AC 208/230 V
AC 208/230 V
3
2
Indoor unit-Outdoor unit S1-S2
*3
AC 208/230 V
AC 208/230 V
AC 208/230 V
AC 208/230 V
AC 208/230 V
AC 208/230 V
3 8
[Indoor unit-Outdoor unit S2-S3
*3
DC 24V
DC 24V
DC 24V
DC 24V
DC 24V
DC 24V
Remote controller-Indoor unit
*3
DC 12V
DC 12V
DC 12V
DC 12V
DC 12V
DC 12V
* . Max. 45 m, 147 ft
if 2.5 mm? used, Max. 50 m, 164 ft
if 2.5 mm? used and S3 separated, Max. 80 m, 262ft
*2. The 10 m, 30 ft wire is attached in the remote controller accessory. Max 1500 ft
*3. The figures are NOT always against the ground.
$3 terminal has DC 24 V against $2 terminal. However between S3 and $1, these terminals are NOT electrically insulataed by the transformer or other device.
*4, Use earth leakage breaker (NV}
Notes:
1.
Wiring size must comply with the applicable local and nationai code.
2.
Use copper supply wires.
3.
Use wires rated 600V or more for the power supply cables and the indoor/outdoor unit connecting cables.
4.
Install an earth longer than other cables.
208/230V
Single phase
lsolator
3 poles isolator
$1
$1
A-Control
$2
Outdoor Unit
$3
$2
A-Control
Indoor Unit
$3
AN Warning:
In case of A-control wiring, there is high voltage potential on the S3 terminal caused
by electrical circuit design that has no electrical insulation between
power
line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, $3 terminals when the power
is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.
7. Test run
7.1. Before test run
» After completing
installation
and the wiring and
piping
of the indoor and
outdoor units, check for refrigerant leakage, looseness in the power supply
or control wiring, wrong
polarity, and no disconnection of one phase in the
supply.
> Use
a 500-volt
megohmmeter
to check
that the
resistance
between
the
power supply terminals and ground is at least 1.0MQ.
» Do not carry out this test on the control wiring (low voltage circuit) terminals.
Warning:
Do not use the air conditioner if the insulation resistance is less than 1.0MQ.
Insulation resistance
After installation or after the power source to the unit has been cut for an extended
period, the insulation resistance will drop below 1 MQ due to refrigerant accumulat-
ing in the compressor. This is not a malfunction. Perform the following procedures.
1. Remove the wires from the compressor and measure the insulation resistance of
the compressor.
2. If the insulation resistance is below
1 MQ, the compressor is faulty or the resis-
tance dropped due the accumulation of refrigerant in the compressor.
3. After connecting the wires to the compressor, the compressor will start to warm
up after power is supplied. After supplying power for the times indicated below,
measure the insulation resistance again.
* The insulation resistance drops due to accumulation of refrigerant in the com-
pressor. The resistance will rise above
1 MQ
after the compressor is warmed
up for two to three hours.
(The time necessary
to warm
up the compressor
varies according
to atmo-
spheric conditions and refrigerant accumulation.)
* To operate the compressor with refrigerant accumulated in the compressor, the
compressor must be warmed
up at least 12 hours to prevent breakdown.
4. If the insulation resistance rises above 1 MQ, the compressor is not faulty.
4\Caution:
« The compressor will not operate unless the power supply phase connection
is correct.
«Turn on the power at least 12 hours before starting operation.
- Starting operation immediately after turning on the main power switch can result
in severe damage
to internal parts. Keep the power switch turned on during the
operational season.
> The followings must be checked as well.
* The outdoor unit is not faulty. LED1
and LED2 on the control board of the outdoor
unit flash when the outdoor unit is faulty.
* Both the gas and liquid stop valves are completely open.
* A protective sheet covers the surface of the DIP switch panel on the control board of
the outdoor unit. Remove the protective sheet to operate the DIP switches easily.
* Make sure that the all of the SW5
DIP switches for function changes on the con-
trol board of the outdoor unit are set to OFF. If all of the SW5 switches are not set
to OFF,
record the settings and then set ail of the switches to OFF.
Begin recov-
ering the refrigerant. After moving the unit fo a new location and completing the
test run, set the SW5 switches to the previously recorded settings.