Pressed key
2nd line on display
Auto
Auto
3.1.4 Parameter setting
The following table shows the setting options and the effects of the individual parameters. A
parameter can be selected via the menu selection
For reasons of safety, the modification mode for the parameters can
only be enabled in the "Stop"- operation (key
1st line on display
base load OFF
base load ON
peak load OFF
peak load ON
high water
(High water HW)
8
The pumps are switched on or off, according to the level
P1 4,7A
requirement. Here, pump P1 is active at the moment.
P2 0,0A
WARNING
2nd line on display
(set value)
Base load off ≤ Peak load
off
and
Base load on ≤ Peak load
on
Peak load on < HW
and
HW ≤ final value of level
sensor
Signification
(see point 3.1.1).
).
Signification
Stop level base load.
Modifications only during Stop-
operation!
Start level base load.
Modifications only during Stop-
operation!
Stop level peak load, 2
nd
off.
Modifications only during Stop-
operation!
Start level peak load, 2
nd
switched on.
Modifications only during Stop-
operation!
Flooding- alarm- level
WARNING
Additionally, this level is constantly
evaluated on the input for the
floating switch HW, independent
from the selected level transmitter.
Thereby, if necessary, 2 different
HV-levels can be realised with 2
different transmitters.
Modification only possible in Stop-
mode !
pump will switched
pump will