Installation instructions
SVM 4001K-A / 4001K-C
Standstill monitoring for 1- and 3-phases motor without sensor
system
Operation Note:
The user must set the switching threshold (EMF limit) and the
ON delay time (T) to ensure that the relays K1 and K2 switch
only at the standstill of the motor.
principle shutdown
Technical Data
Input data
Power supply
Current drain at UN
Maximal voltage at L1, L2, L3
Maximal current drain/ Frequency
L1, L2, L3 with 690 V AC
Output data
Minimal switching current: contacts
Maximal switching current: contacts
Switching capacity, switching cycles
IEC/EN 60947-4-1
IEC/EN 60947-5-1
Mechanical life switching cycles
Contact material
Contact fusing
Maximal switching cycles AC15/ DC13
Rated insulation voltage
Impulse withstand voltage
Typical reaction time
Typical dropout time
Environment data
Environment temperature
Storage temperature
Vibration resistance 3 axis
Duty cycle
Air and creep age distance
Protection class
Housing material
Doc. # BA000926 – 02/2017 (Rev. D)
(translation from original)
SVM 4001K-A / 4001K-C
Contact durability
7
10
AC1
230V
AC15
6
230V
10
5
10
4
10
0.1
Schaltstrom (A) / Switching current (A)
Switching Current (A)
24 V DC –15 +10 %
150 mA
690 V AC
0,35 mA / 5 kHz
10 mA
8 A
AC1: 230 V / 8 A, 100 000
DC1: 24 V / 8 A, 100 000
AC15: 230 V / 3 A,
DC13: 24 V / 4 A
> 20 x 10
6
AgNi10
5 A slow
360 / h at max. switching current AC15 / DC13
250 V AC
4 kV, pollution degree 2
20 ms
20 ms
-20 to +55°C
DIN IEC 60068-2-3
-40 to +70°C
DIN IEC 60068-2-3
Sinus 10–55 Hz, 0,35 mm, 10 cycles, 1 octave / min
100 %
DIN EN 50178,
safe isolation
installation in a closed cabinet only with min. IP 54
PC Makrolon
DC1
24V
DC13
24V
0.5
1.0
2.0
3.0 4.0 5 6 10
EN 12