800VA/480W StandBy PDU UPS
IMPORTANT SAFETY INSTRUCTIONS
ATTENTION!
This manual contains important safety instructions. Please follow all instructions carefully during installation. Read this
manual thoroughly before attempting to unpack, install or operate.
The UPS may only be repaired by qualified personnel.
The battery warranty is 1 year from the date of purchase.
Caution: Any changes or modifications to the equipment not expressly approved by the party responsible for
compliance could void the user's authority to operate the equipment.
Shielded interface cables and AC power cords, if any, must be used in order to comply with the emission limits.
Caution: To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area,
free of conductive contaminants.
Caution: Risk of electric shock, do not remove the cover. No user serviceable parts. The UPS system operates with
hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.
Caution: Connect the UPS system only to an earthed shockproof outlet which must be easily accessible and close to
the UPS system.
Caution: The UPS must be connected to a wall receptacle with ground connection (2 pole, 3 wire grounded
receptacle (wall outlet).)
Caution: Risk of electric shock, hazardous live parts inside this UPS can be energized from the battery supply even
when the input AC power is disconnected.
Caution: Risk of electric shock, Battery Circuit is not isolated from AC input, hazardous voltage may exist between
battery terminals and ground. Test before touching.
Caution: Do not install the UPS system near water or in moist environments.
Caution: Do not install the UPS system where it would be exposed to direct sunlight or near heater.
Caution: Do not block ventilation holes in the UPS housing (if present).
Caution: The UPS is designed to be for use with computer loads only. Do not connect a laser printer to the outlets.
Do not connect domestic appliances such as hair dryers to UPS output sockets.
Caution: Please use only CE-marked mains cable (e.g. the mains cable of your computer) to connect the UPS system
to the building wiring outlet (shockproof outlet).
Caution: Please use only CE-marked power cables to connect the loads to the UPS system.
Caution: Prevent no fluids or other foreign objects from inside of the UPS system.
Caution: In a domestic environment, this product may cause radio interference, in which case the user may be
required to take adequate measures.
Caution: Do not try to repair the unit yourself, contact your local supplier or your warranty will be void.
Caution: Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no
current is present and no hazardous voltage exists in the terminals of high capability capacitor such as BUS-capacitors.
Caution: Place cables in such a way that no one can step on or trip over them.
Caution: Do not disconnect the mains cable on the UPS system or the building wiring outlet (shockproof socket
outlet) during operations since this would cancel the protective earthing of the UPS system and of all connected loads.
TRANSPORTATION
Please transport the UPS system only in the original package to protect against shock and impact.
PPREPARATION
Condensation may occur if the UPS system is moved directly from cold to warm environment. The UPS system must
be absolutely dry before being installed. Please allow at least four (5) hours for the UPS system to acclimate the
environment.
This equipment, due to unique limitations due to peak current, may not be suitable for equipment
with active PFC (active power factor correction). Please check in advance the type of power
supply installed your PC/Server.
INSTALLATION
PACKAGE CONTENTS
Make sure that you have the following items: UPS, schuko cable, Rack Kit, Manual, Warranty. If any of the above
items are missing, please contact your reseller.
INSTALLATION
Follow all instructions carefully during installation. Read the entire manual carefully before starting to install the
device. Keep this manual for future reference.
1. PLACEMENT and RACK MOUNTING
To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area, free of
conductive contaminants.
 This UPS system is designed for indoor use only.
 Do not install the UPS under direct sunlight. Your warranty will be void if the batteries fail due to overheating.
 Install in a temperature and humidity controlled indoor area
Fix the brackets to the product using the appropriate screws and then attach them to the Rack cabinet structure.
The Rack Kit included consists of 2 brackets and 8 screws for fixing these to the UPS structure.
2. MAINS CONNECTION AND BATTERY CHARGING
Connect the UPS to a wall outlet using the cable included in the package. Avoid the use of extension cords and
adapters. We recommend charging the battery for at least 8 hours to ensure that it is fully charged. To recharge the
battery, simply the power cable must be plugged into a wall outlet. To maintain optimum battery charge, the UPS
must be connected to a wall outlet at all times, as this UPS can be charged even when it is not switched on.
3. LOAD CONNECTION
Connect loads to the outputs (located on the rear and front panel) of the UPS. All outputs are in backup/protection
mode and therefore protect the load and supply it when the mains power fails. It is recommended to connect a load
not exceeding 80-85% of the maximum allowed value (in Watts) to the device. Only connect your computer, monitor
and any externally powered data storage device (hard disk, tape drive, etc.) to the sockets when the UPS is switched
off and disconnected. Do not connect a laser printer, copier, heater, hoover, shredder or other large electrical devices
to the UPS. The power requirements of these devices will overload and may damage the unit.
MANUAL
A03-PDU1000-RC_ME(11-23)
OVERVIEW
FRONT PANEL and REAR PANEL
1: Power on/off button: To turn on the UPS press the button for a couple of seconds, the system will beep 2
times (LED lit green). To turn off the UPS press the button for a couple of seconds, the system will beep 3 times.
2: LED: The LED is lit when the UPS is running, it flashes when in battery/overload mode.
3: Output Sockets: There are 8 Schuko outlets (including 2 at the rear) to which critical loads can be
connected.
4: Mains Inlet (AC Inlet): Connect the device to the mains power supply via the schuko cable. The electrical
system to which the UPS is connected must support earthing.
5: USB Port: USB connector (connect via the appropriate cable, not included, to the PC). The SW (PowerMaster)
is available at the following link: www.atlantis-land.com/softwareups
6: EPO port: Enables emergency shutdown of the UPS from a remote location. If the EPO terminal is open, the
UPS will shut down and the outputs will shut down immediately.
7: Input Circuit Breaker (ICB): Input overcurrent protection system. To protect the UPS, the system breaks
the circuit (like a fuse). To reset the circuit, press the red button.
LED/ALARM
STATUS
LED Status
Normal (AC)
LED on
Battery Discharge
LED flashing
Battery Low
LED flashing
Overload
LED ON/flashing
STARTUP and TEST
Mains Mode(AC Mode)
The UPS supplies power to all connected load by filtering the power grid and maintains the battery charge.
Battery Mode(On-Battery Mode)
The UPS operates using the battery when the mains voltage is out of tolerance or when it is completely absent (black
out). Visual and audible indicators signal this mode of operation. The UPS powers the load, using battery power,
producing an approximate sinusoidal output voltage.
1.
Power On/Off : Press, a couple of seconds, to turn the device on/off. The LED lights up and a double beep
sounds. The loads are now energized (see points 3 and 4 in the previous picture) [Optional] You can check the
correct operation of the battery mode by disconnecting, with ups on, the mains connection cable. The LED will
start flashing and beeping while the load is properly powered. Connect the power cord back to the mains to
restore normal operation. The beep can be muted by installing the control SW (UPS Setting->Configuration and
setting Utility Power Failure Alarm=Disabled).
2.
Cold Start/Start on Battery: It is possible to turn on the UPS in case of power failure and directly power the
load. This "DC-Start/Cold-Start" feature requires the connected load to be less than 80% of the maximum load (it
is important to turn on all peripherals first and the UPS last. In fact, the load must remain constant).
MAINTENANCE and STORAGE
MAINTENANCE
 To clean the panel and plastic parts, use soft, dry cloths. Do not use cleaning agents containing alcoholic
substances.
 Unplug the UPS from the power outlet if the UPS will not operate for an extended period of time.
STORAGE
 First turn off the UPS and unplug the power cord from the power outlet. Disconnect all cables connected to the UPS
to avoid draining the battery.
 The UPS should be stored in a cool, dry place.
 Ensure that the battery is fully charged before storing the UPS.
 For prolonged storage in moderate climates, the battery must be charged for 12 hours every 3 months by plugging
the power cord into the wall socket and turning on the main button. Repeat this every 2 months if the UPS is stored
in a high temperature location.
TROUBLE SHOOTING
Problem
Possible Causes
Mains power is not reaching the UPS. Check that the power cable is properly
Power supply is present but
the UPS does not operate in
mains mode (AC Mode).
ICB circuit activated.
The ICB has tripped due to an
overload.
The load is not supplied.
The batteries are discharged.
The unit has been damaged
by a violent overcurrent or extreme
voltage spike.
Backup Time is very limited.
The batteries are not fully charged or
are nearing the end of their life cycle.
The software does not seem
The serial/USB connection cable is not
to
communicate
with
the
connected.
device.
The unit does not provide battery power.
If abnormal situations not listed above occur, contact Atlantis technical support.
DOWNLOAD SOFTWARE
The PowerMaster Local management software, which is available for the most popular operating systems, allows both
configuration and information on the operating status of the UPS and the controlled shutdown of the connected PC.
The PowerMaster software is available at the following link: www.atlantis-land.com/softwareups
Download the appropriate version for your operating system, install it and restart your personal computer.
SUPPORT
For technical questions and support, please contact our help-desk by ticket on http://www.atlantis-
land.com/ita/supporto.php.
For generic informations, please send an e-mail to info@atlantis-land.com.
presales informations, please send an e-mail to prevendite@atlantis-land.com.
Atlantis
Fax: +39.02.84.16.00.19, Website: https://www.atlantis-land.com, Email: info@atlantis-land.com
ALARM
OFF
Beep once every 30 seconds
Beep once every 2 seconds
Beep once every 0.5 seconds/long beep
Solution
connected.
Disconnect the UPS power cable then press
the ICB and reconnect the power cable.
Turn off the UPS and disconnect at least one
of the connected loads. Disconnect the UPS
power cord then press the ICB and reconnect
the power cord.
Allow the unit to recharge for at least 4
hours.
Contact Atlantis technical support.
Recharge the UPS for 10 hours.
Replace
the
batteries
(Contact
Atlantis
technical support).
Connect the USB cable to the UPS unit
and to a free USB port on the computer. The
connection cable is not supplied with the unit.
Switch off the computer and then switch off
the UPS unit. Wait 10 seconds and
switch the UPS back on. This should reset the
unit.
For