Ferroli PEGASUS D Instrucciones De Uso página 32

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Opening the front panel
To open the front panel, see the sequence in fig. 18.
B
Before carrying out any operation inside the boiler, disconnect the electrical
power supply and close the gas cock upstream.
fig. 18 - Front panel opening
Cleaning the boiler and flue
To clean the boiler properly (fig. 19):
Close the gas cock ahead of the boiler and disconnect the electrical power.
Remove the front panel of the boiler.
Lift the casing cover by pressing upwards.
Remove the insulation placed over the anti-backflow device.
Remove the fume chamber closing plate.
Remove the burner assembly (see next section).
Clean from the top downwards, using a flue brush.
Clean the fume evacuation ducts between the cast iron elements of the boiler shell
with a vacuum cleaner.
Carefully refit all the previously removed parts and check the tightness of the gas
circuit and the combustion ducts.
During cleaning operations be careful not to damage the fume thermostat bulb at
the back of the fume chamber.
fig. 19 - Boiler cleaning
1
Casing cover
2
Fume chamber closing plate
3
Flue brush
7
Combustion analysis plug
Combustion analysis
A point for sampling fumes has been included inside the boiler, in the upper part of the
anti-backflow device (detail 7 - fig. 19).
To take the sample:
1.
Remove the upper panel of the boiler
2.
Remove the insulation placed over the anti-backflow device;
3.
Open the fume sampling point;
4.
Insert the probe;
5.
Activate the TEST mode
6.
Wait 10-15 minutes for the boiler to stabilise*
7.
Take the measurement.
Analyses made with an unstabilised boiler can cause measurement errors.
A
32
EN
Removing and cleaning the burner assembly
To remove the burner assembly:
Disconnect the electrical power supply and turn off the gas ahead of the boiler;
Undo the nut fixing the gas supply pipe ahead of the gas valve;
Undo the two nuts fixing the combustion chamber door to the cast iron elements of
the boiler (fig. 20)
Remove the burner assembly and combustion chamber door.
Then check and clean the main burners and pilot burner. Use a non-metal brush or com-
pressed air to clean the burners; never use chemical products.
Pilot burner assembly
1
2
7
3
1
Combustion chamber door
2
Inspection door
3
Pilot burner
4
Ignition electrode
5
Detection electrode
6
Pilot nozzle
7
High voltage cable
8
Gas supply pipe
cod. 3540U171 - 06/2012 (Rev. 00)
PEGASUS D
fig. 20 - Removing the burners
3 ÷ 4 mm
3
4
5
8
fig. 21 - Pilot burner

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Pegasus d seriePegasus d 23Pegasus d 32Pegasus d 45

Tabla de contenido