5. Design guidelines
76
5.B. Boiler room requirements
а) Boiler foundation min. 0.05 m
Boiler foundation requirements:
the foundation must protrude over the boiler room floor
the foundation edges must be secured with steel angle sections
b) Boiler room floor
Boiler room floor requirements:
the boiler room floor must be made of non-flammable materials, resistant
to extreme temperature changes and impact
the floor must descend in the well direction
c) Boiler room ventilation
Boiler room ventilation requirements:
do not use mechanical ventilation system in the room with solid fuel furnace
if the combustion air is supplied directly from the room and the flue gas is
discharged gravitationally via a duct from the device
the boiler room must be fitted with a ventilation duct with a cross section of
at least 50% of the flue cross sectional area, min. 20x20 cm
the boiler room must be fitted with a ventilation duct with a cross section
of at least 25% of the flue cross sectional area with the outlet under the
boiler room ceiling
the outlet duct cross section must be min. 14x14 cm
the vents must be made of non-flammable materials.
5.C Hydraulic system requirements
the hydraulic system must be made in accordance with good building
practices, relevant standards and regulations, and the design input
the boiler may operate in a sealed heating system (sealed diaphragm tank)
provided that the boiler supply and return line is fitted with a dual action
relief valve
a pressure reducer must be installed with a relief valve to avoid safety valve
opening in case of a rapid increase in boiler water pressure
an expansion tank must be installed in the highest point of the heating
system and protected against frost
the expansion tank should be installed at the boiler return
to guarantee proper working conditions and failure free boiler operation,
ensure a minimum temperature at the boiler return by installing the boiler
pump with a mixing valve (boiler mixing system)*
a temperature sensor of the system protecting against exceeding permissi-
ble temperatures must be installed directly on the boiler
the boiler is compatible with water as a medium conforming to water
quality requirements.
Experts in biomass heating
* Water temperature at the boiler return must be min.
45°C to prevent boiler corrosion as a result of undesirable
and excessive flue gas condensation in the boiler.
for that purpose the boiler circulation pump must be
fitted with a control valve. The pump output must be
approx. 40÷50% of the nominal water flow through the
boiler. The boiler circuit design must ensure that the
difference in temperature between the supply and the
return does not exceed 15°C.
CAUTION!
The boiler pump must be installed between two cut-off
2
valves. To protect the pump against high pressure
difference between the suction and discharge:
• install the boiler pump at the system return (especially
in systems with high water capacity, where the
discharge pressure is very high)
• protect the boiler pump at the suction against
low pressure.