8. Functions – Settings by DIP switch 4.
Factory settings
DIP 1: OFF
DIP 2: OFF
DIP 3: OFF
DIP 4: ON
DIP 5: OFF
COM 1 + COM 2
DIP 1
Normal mode / Test mode (NORM / TEST)
Test mode has priority over all
other settings on the presence
detector and serves the pur-
pose of checking for proper
working order as well for testing
the detection zone. Irrespective
DIP 2
Semi-automatic mode (MAN) / fully automatic mode (AUTO)
Semi-automatic mode: (MAN)
The light now only switches
OFF automatically. Light is
switched ON manually.
Fully automatic mode: (AUTO)
The light automatically switches
ON and OFF in relation to light
level when someone is present.
Light can be switched ON
and OFF manually at any time.
This temporarily interrupts the
DIP 3
Button / switch
Tells the sensor how to interpret
the incoming signal. Assigning
external buttons / switches
allows you to operate the
detector as a semi-automatic
unit and override it manually at
any time.
DIP 4
ON / ON-OFF button
In the ON-OFF setting, the light
can be switched ON and OFF
manually at any time (except in
pulse mode: no manual OFF).
DIP 6: ON
DIP 7: OFF
DIP 8: OFF
Light-level setting e:
Time setting 6.: 15 min.
of ambient light level, the pres-
ence detector activates the light
to stay ON for approx. 8 sec. in
response to movement in the
room. (blue LED flashes when
movement is detected).
Light must be requested using
the button and stays ON for the
time set at the potentiometer
automatic switching function.
Irrespective of the settings
selected, light stays ON for 4
hours after manually pressing
the button twice or switches
OFF after manually pressing
• Operation either by button or
switch
• Several buttons possible on
one control input
• Only use illuminated push-
button with neutral conductor
connected
In the ON setting, light can
no longer be switched OFF
manually.
- 24 -
Stay-ON time g: 30 min.
Switch-ON delay h: 5 min.
Reach setting i: centre
Basic light level o: 30 min.
All user-selected potentiom-
eter settings apply in normal
mode. The presence detector
can also be set by means of
the blue LED without any load
connected.
(pressing twice switches ON for
4 hours).
the button once. Pressing the
button before the
4 hours elapse returns the
presence detectors to the nor-
mal operating mode.
• Cable length between sensor
and switch < 50 m
The stay-ON time starts from
the beginning again each time
the button is pressed.