A 230V~ alarm signal can be obtained when
the overheat protection is triggered (or
temperature limiter for PNT20/30/305).
• PNT15/135: between terminals 1 and 13
• PNT20/30/305: between terminals 1 and 12
Controls are connected via grommets on the
back of the unit to assigned terminal blocks.
When connecting external accessories or
secondary units, the links must be adjusted
according to relevant wiring diagram.
See wiring diagrams.
Start-up
When the unit is used for the first time or after
a long period of non-use, smoke or an odour
may result from dust or dirt which has collected
on the element. This is completely normal and
disappears after a short time.
Overheating
The fan heater is equipped with an overheat
protection. If it is deployed due to overheating,
reset as follows:
1. Disconnect the power supply with the isolator
switch.
2. Determine the cause of overheating and
rectify the fault.
3. Reset by opening the lid and pushing the red
button on top of the overheat protection until
a click sound is heard. See pictures in the
introduction pages.
4. Put the lid back on and reconnect the heater.
NOTE! All work inside the unit's connection area
must be carried out by a qualified technician and
with the power supply disconnected.
Maintenance
Since fan motors and other components are
maintenance-free, no maintenance other than
cleaning is necessary. The level of cleaning can
vary depending on local conditions. Undertake
cleaning at least twice a year. Inlet and exhaust
grilles, impeller and elements can be vacuum
cleaned or wiped using a damp cloth. Use a
brush when vacuuming to prevent damaging
sensitive parts. Avoid the use of strong alkaline
or acidic cleaning agents.
Residual current circuit breaker
When the installation is protected by means of
a residual current circuit breaker, which trips
when the appliance is connected, this may be
due to moisture in the heating element. When
an appliance containing a heater element has
Get In Touch
Call: 0845 6880112
Email: info@adremit.co.uk
Panther T
not been used for a long period or stored in
a damp environment, moisture can enter the
element.
This should not be seen as a fault, but is
simply rectified by connecting the appliance to
the main supply via a socket without a safety
cut-out so that the moisture can be eliminated
from the element. The drying time can vary
from a few hours to a few days. As a preventive
measure, the unit should occasionally be run
for a short time when it is not being used for
extended periods of time.
Packaging
Packaging materials are chosen with
consideration to the environment and are
therefore recyclable.
Handling of product at end of working
life
This product may contain substances necessary
for the functionality of the product but
potentially dangerous for the environment. The
product should not be disposed of mixed with
general household waste but delivered to a
designated collection point for environmental
recycling. Please contact the local authority
for further details of your nearest designated
collection point.
Safety
• For all installations of electrically heated
products a residual current circuit breaker
300 mA for fire protection should be used.
• Keep the areas around the air intake and
exhaust grilles free from possible obstructions!
• The unit must not be fully or partially covered as
overheating can result in a fire risk!
• The unit must not be placed directly under fixed
wall sockets!
• This appliance can be used by children aged
from 8 years and above and persons with
reduced physical, sensory or mental capabilities
or lack of experience and knowledge if they
have been given supervision or instruction
concerning use of the appliance in a safe way
and understand the hazards involved. Children
shall not play with the appliance. Cleaning and
user maintenance shall not be made by children
without supervision.
• Children of less than 3 years should be kept
away unless continuously supervised.
• Children aged from 3 years and less than 8
years shall only switch on/off the appliance
provided that it has been placed or installed
Our Address