E
N
THREE-PHASE STANDARD CONNECTION (default) Default wiring configuration for standard applications.
Voltage measure
Current measure
Phase angle offset
Capacitor overload current measure
Parameter setting
For three-phase connection, the voltage input must be connected phase to phase; the current transformer must be
connected on the remaining phase.
The polarity of the current/voltage input is indifferent.
Tel.+39 051 6618311 Fax +39 051 6605594 E-mail: italfarad@italfarad.com Web: www.italfarad.com
Wiring diagrams
Disconnect the line and the supply when operating on terminals.
Standard three-phase wiring
PFC144evo
ITALFARAD S.p.A. via IV novembre n.1 Minerbio Bo Italy
WARNING!
1 ph-to-ph voltage reading L2-L3
L1 phase
Between V (L2-L3 ) and I (L1) 90°
1 reading calculated on L2-L3
P.03 = L1
P.05 = L2-L3
P.24 = 3PH
NOTES
60