DIP switch reset
1.1.6
ON
1
2
3
4
5
6
7
8
1.1.1 Sensor calibration: DIP switch 1
Set the DIP switch to ON and press the DIP switch reset button:
The display shows CAL. The room temperature currently acquired
blinks.
Press
or
to make a recalibration of max. ± 5 °C. To save
the entry, set the DIP switch to OFF and press the DIP switch reset
button (also refer to Fig.
).
1.1.2 Setpoint limitation: DIP switch 2
DIP switch ON:
Setpoint limitation 16...35 °C
DIP switch OFF:
Setpoint limitation 3...35 °C
(factory setting)
Save the entry by pressing the DIP switch reset button.
1.1.3 Temperature display in °C or °F:
DIP switch 3
DIP switch ON:
Temperature display in °F
DIP switch OFF:
Temperature display in °C
(factory setting)
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
).
1.1.4 Control action: DIP switches 4 and 5
DIP switch 4 ON and 5 ON:
Adaptive control for all types of application.
DIP switch 4 ON and 5 OFF:
2
Accessing the expert level
Move the selector slider to the RUN position and press simultaneously
seconds, press simultaneously
access the expert level for making the settings on that level.
Starting with code 00, the display shows the choice of languages. Navigation on the expert level is made possible with
settings by pressing
.
The expert level is quit by pressing the operating mode selection button
Code list
Function block
Basic settings
LCD settings
Clock settings
Note 1:
If the radio clock is not active or not present, this setting has no impact.
With the radio clock active, the time signal received from Frankfurt is shifted by the value set under code 30 (time zone).
Note 2:
If the radio clock is not active or not present, the time change always takes place at 02:00 on the Sunday before the set date.
With the radio clock active, the time change is shifted by the value set under code 30 (time zone).
Note 3:
If the radio clock is not active or not present, the time change always takes place at 03:00 on the Sunday before the set date.
With the radio clock active, the time change is shifted by the value set under code 30 (time zone).
6/40
When changing one or several DIP switch positions, a DIP switch reset must be made by
pressing the DIP switch reset button (also refer to Fig.
9
Otherwise, the previous settings will be maintained!
Factory setting: All DIP switches
PID self-learning
PID 6
and
for 3 seconds, release
Code
Name
00
Language
01
Sensor calibration
02
Switching differential 2-point
10
Illumination time
11
Background brightness
12
Contrast
Time zone
Deviation from time signal received from
30
Frankfurt (Central European Time CET)
(refer to Note 1)
31
Start of summer time (refer to Note 2)
32
End of summer time (refer to Note 3)
OFF
For fast controlled systems, applications at locations with
great temperature variations.
DIP switch 4 OFF and 5 ON:
For normal controlled systems, applications at locations
with normal temperature variations.
DIP switch 4 OFF and 5 OFF:
For difficult controlled systems, 2-position controller with a
switching differential of 0.5 °C (factory setting).
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
1.1.5 Radio clock: DIP switch 6
Can only be used with REV..DC (with integrated DCF77 receiver for
time signal from Frankfurt)!
DIP switch ON:
DIP switch OFF:
Save the entry by pressing the DIP switch reset button
(also refer to Fig.
1.1.6 DIP switch reset
When changing one or several DIP switch positions, press the DIP
switch reset button to make a DIP switch reset.
Otherwise, the previous settings will be maintained!
(Also refer to Fig.
and
for 3 seconds, then release the buttons and, within 3
and keep
depressed for another 3 seconds. This enables you to
on display (also refer to Fig. G).
.
Factory setting
English
off
0.5 °C
10 seconds
0
0
0 hours
March 31 (31-03)
October 31 (31-10)
08.02.2008
).
PID 12
2-Point
).
quartz
Clock runs on built-in
Time signal DCF77 from
Frankfurt
).
).
and
Your setting
. Confirm the
CE1G2201xx