Output charts water AREC4000W
Metric chart
Type
Fan
position
AREC4010W-NA
max
AREC4015W-NA
max
AREC4020W-NA
max
AREC4025W-NA
max
Type
Fan
position
AREC4010W-NA
max
AREC4015W-NA
max
AREC4020W-NA
max
AREC4025W-NA
max
*
) Recommended outlet air temperature for good comfort and optimized output.
1
*
) Nominal output at given supply and return water temperature.
2
Imperial chart
Type
Fan
position
AREC4010W-NA max
AREC4015W-NA max
AREC4020W-NA max
AREC4025W-NA max
Type
Fan
position
AREC4010W-NA max
AREC4015W-NA max
AREC4020W-NA max
AREC4025W-NA max
*
) Recommended outlet air temperature for good comfort and optimized output.
1
*
) Nominal output at given supply and return water temperature.
2
6
Supply water temperature:80 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
Airflow
Output
Return
water
temp.
[m
/h]
[kW]
[°C]
3
2550
14.7
31
3300
18.9
35
4700
27.8
30
5700
32.3
27
Supply water temperature: 60 °C
Room temperature: +18 °C
Outlet air temperature: +35 °C*
Airflow
Output
Return
water
temp.
[m
/h]
[kW]
[°C]
3
2550
15.2
37
3300
18.8
33
4700
27.7
35
5700
32.6
35
Supply water temperature:176 °F
Room temperature: +64 °F
Outlet air temperature: +95 °F*
Airflow
Output
Return
water
temp.
[cfm]
[MBH]
[°F]
1501
50.2
88
1942
64.5
95
2766
94.9
86
3355
110.2
81
Supply water temperature: 140 °F
Room temperature: +64 °F
Outlet air temperature: +95 °F*
Airflow
Output
Return
water
temp.
[cfm]
[MBH]
[°F]
1501
51.9
99
1942
64.2
91
2766
94.5
95
3355
111.3
95
AREC4000
1
Water
Pressure
flow
drop
[l/s]
[kPa]
0.07
2.6
0.09
1.6
0.13
1.5
0.15
2.2
1
Water
Pressure
flow
drop
[l/s]
[kPa]
0.16
11.2
0.17
5.1
0.27
5.3
0.28
7.2
Water temperature: 176/140 °F
Room temperature: +64 °F
1
Water
Pressure
Output *
flow
drop
[US gal/h]
[kPa]
[MBH]
68.5
2.6
95.9
84.6
1.6
134.5
127.5
1.5
189.1
142.7
2.2
236.5
Water temperature: 140/104 °F
Room temperature: +64 °F
1
Water
Pressure
Output *
flow
drop
[US gal/h]
[kPa]
[MBH]
155.0
11.2
55.6
163.6
5.1
78.2
252.0
5.3
110.2
266.3
7.2
136.9
Water temperature: 80/60 °C
Room temperature: +18 °C
Output*
Outlet
Water
2
air temp.
flow
[kW]
[°C]
[l/s]
28.1
50
0.34
39.4
53
0.48
55.4
53
0.68
69.3
54
0.85
Water temperature: 60/40 °C
Room temperature: +18 °C
Output*
Outlet
Water
2
air temp.
flow
[kW]
[°C]
[l/s]
16.3
37
0.20
22.9
38
0.28
32.3
38
0.39
40.1
39
0.49
Outlet
Water
2
air temp.
flow
[°F]
[US gal/h]
122
326.2
127
456.5
127
643.0
129
808.5
Outlet
Water
2
air temp.
flow
[°F]
[US gal/h]
99
187.4
100
264.4
100
370.9
102
466.1
Pressure
drop
[kPa]
39.6
29.5
25.9
46.5
Pressure
drop
[kPa]
15.8
11.8
10.3
19.0
Pressure
drop
[kPa]
39.6
29.5
25.9
46.5
Pressure
drop
[kPa]
15.8
11.8
10.3
19.0