Wiring
Do not apply power to the UPS until installation is totally
completed.
Do not make unauthorized changes to the UPS; otherwise,
damage may occur to your equipment and void your warranty.
Input Wiring
PX1.5, 2.5K HV(220V/230V240V) Model comes with input
cable with plug. Plug the input cable to appropriate mains
supply socket.
Note the voltage and current rating of the product. Refer to below table for input wiring
Model
CRA 6012
CRA 6025
CRA 6040
CRA 6060
Even internal over current protection breaker is embedded in the product, external switchable circuit breaker
should be installed at upstream of the UPS product for safe installation and maintenance of product.
Output Wiring
The input of the equipment needs to be protected by UPS should connect to the UPS output
Single Phase 220V Mode Wiring
To have single 220V output, connect the Jumper
between terminal H2, H3(default status). Then you can
have Dual independent phase between H1& H4.
32
Nominal Input
Voltage
220V/230V/240V
220V/230V/240V
220V/230V/240V
220V/230V/240V
Rated Input
Current
11A
16A
32A
32A
EN
Input Cable
AWG/Cross-section
14AWG/2mm2
14AWG/2mm2
10AWG/6mm2
10AWG/6mm2