When UPS Work on Bypass or Standby Mode, Press the Setting Enter Button for 5 seconds, the UPS enter setting
mode, accept setting of output voltage, frequency, battery number, bypass enable/disable, ECO mode enable
/disable, EPO function ON/OFF.
Use Up page and down Page to change the setting . and short press the setting for confirm the change
After setting, turn off the mains power supply, wait the UPS turn off under battery mode until display if total
off,
turn on the UPS again to activate the setting change.
Battery Self-test
In Normal mode, press the Up Page Button for more than 4 seconds until the buzzer beeps. he UPS switch to
battery test mode, to check the status of the battery, the UPS exit the battery test mode if the battery abnormal
and present alarm with the battery icon flashing. If test mode end up with normal, the UPS switch to normal
mode automatically.
Buzzer Mute
When UPS is on battery or bypass mode, UPS will warn with warning tone (Battery mode four seconds one tone;
Bypass mode two minutes. You can disable or enable the buzzer tone manually.
In the battery and bypass mode, push Down Page button for about 4 seconds until you here a buzzer beep. the
buzzer alarm can be muted. Press the button for 4seconds again to recover the buzzer alarm function.
The Buzzer Muting is valid only in battery mode, and invalid for any other UPS alarm .
MAINTENANCE
Routine Maintain
To make sure UPS work normal, appropriate maintenance should be schedule periodical , below items should be
checked:
Check UPS running status.
If the utility power is normal, UPS should work in line mode or in battery mode. And there is
no warning or fault
indication.
Check UPS running mode switch.
Cut off the line input to simulate the utility power interrupt, UPS should transfer to battery mode, and connect the
line input, UPS return to line mode again.