UPS Output Short-Circuit
22
23
29
UPS Input rectifier protection
57
59
60
Battery Icon Flashing
UPS not working normal line mode
With normal mains input
Backup time is not as long as expected
UPS not turn ON after pressing
ON/OFF button
40
UPS Over Load
UPS Over Temperature
Battery UN-connected
Charger Fail
EPO activated
UPS Internal failure, Contact distributor for
service.
Remove short-circuit equipment from UPS.
Reduce loading capacity below UPS rating.
Make sure UPS should work in ambient of -
10-45oC, if the ambient temperature can't meet
this spec. Try reduce loading.
Check ventilation inlet of the UPS ON from panel
and outlet on the rear panel is not blocked.
UPS Internal failure, Contact distributor for
service.
Low input voltage and overload.
UPS Internal failure, Contact distributor for
service.
Check battery input wiring and battery cutoff
device such as circuit breaker etc.
UPS Internal failure, Contact distributor for
service.
Reset the External EPO switch, if no EPO switch
install, turn off EPO function via the operating
panel.
Battery not connected or battery low.
Charger failure, Contact distributor for service.
Make sure Input circuit breaker is ON.
Turn on the UPS via ON/OFF button.
Battery low, recharge the battery long enough
time.
Overload, reduce the loading.
Battery aged, Contact distributor for service.
Press the ON/OFF button long enough time,
3seconds, and hear a buzzer
acknowledging the correct TURN ON operation.
Battery low or not connected.
UPS Internal failure, Contact distributor for
service.