Installation
Oil feeding and suction line
Burner lower than tank
y
Burner higher than tank
Burner higher than tank
H
Y must be kept as lower as possible in order to avoid cavitation. Anyway Y< 4 m.
Pump in suction (H +) or charging (H )
Altitude (m)
0500
501800
8011300
13011800
18012200
e.g.: altitude 1100m Theoretical H = 1m actual H 2m, Corrected H for suction 2 + 1 = 3m Corrected H for charging 2 - 1 = 1m.
Choose the Ø of the piping from the table, based on the length expanded between the tank and pump. If corrected H for suction
exceeds 4m; make provisions for a transfer pump (max. pressure 2 bar).
420010580401
H = x-y
x
Correction of altitude
Theoretical H (m)
0
0,5
1,0
1,5
2,0
FEEDING LINE WITH SUNTEC D 57 A
Pipe length (m)
Length pipe (m)
H
(m)
ø 8 mm
0
37
0,5
42
1
47
2
65
3
65
4
74
N.B. = X < 20 m
Length pipe (m)
H
Pipe length (m)
(m)
ø 8 mm
0
37
0,5
33
1
28
2
19
3
10
4
0
The length of the tubes apply to
!
burners powered by 50 Hz mains
electricity; in case of 60 Hz power,
divide the relevant lengths by 1.5.
www.ecoflamburners.com
ø 10 mm
ø 12 mm
95
150
107
150
118
150
150
150
150
150
150
150
ø 10 mm
ø 12 mm
95
150
84
150
73
150
50
107
27
60
5
13
13
EN