Temper KOBAN K KSAI-6000 ON Manual De Instrucciones página 49

Publicidad

Idiomas disponibles

Idiomas disponibles

Product Description
1.5.4 Battery Charger
The battery charger utilizes energy from the DC bus and precisely regulates it to continuously charge
the batteries. The batteries are being charged whenever the UPS is connected to utility power.
1.5.5 DC-to-DC Converter
The DC-to-DC converter utilizes energy from the battery system and raises the DC voltage to the
optimum operating voltage for the inverter. The converter includes boost circuit which is also used
as PFC.
1.5.6 Battery
The 6K/10K Standard include value-regulated, non-spillable, lead acid batteries inside. To maintain
battery design life, operate the UPS in an ambient temperature of 15-25C.
1.5.7 Static Bypass
The UPS provides an alternate path for utility power to the connected load in the unlikely event of a
UPS malfunction. Should the UPS have an overload, over temperature or any other failure condition,
the UPS automatically transfers the connected load to bypass. Bypass operation is indicated by an
audible alarm and illuminated amber Bypass LED. To manually transfer the connected load from the
inverter to bypass, press the ON/OFF button once.
NOTICE:The bypass power path does NOT protect the connected equipment from disturbances in
the utility supply.
1.6 UPS Working Mode
Normally UPS working mode include normal mode, bypass mode, battery mode, ECO mode,
frequency converter mode, self aging mode.
Normal mode:
Shown as Fig 1-4, rectifier supply DC supply to inverter, the load is feed by inverter. Charger is
charging the battery.
BYPASS
TVS&RFI/E
REC/PFC
INV
MI filter
input
CHG
BATT
High Performance 6-10k UPS
7