Annex D. Battery Run Time
Standard battery pack includes 16 blocks 9AH batteries. Please refer to the table below for the battery
runtime to configure battery packs.
Pack's
UPS
Backup Time (mins)
number
1KW
1
6k
60
10k
60
2
6k
180
10k
180
3
6k
240
10k
240
4
6k
360
10k
360
5
6k
480
10k
480
NOTICE: Backup time of batteries is depending on other facts such as battery brand, working
temperature, working time and so on, the table is calculated according to ideal situation.
NOTICE: Set charger current according to battery capacity, the charger current should not be larger
than 0.2C, normally the charger current is set as 0.1C. Too large charger current could damage the
batteries.