The second screen displays:
Time delay for alarm activating (0 - 180 seconds); 
Delay:
In ATEX version default value is "0".
Hysteresis:
Defines Alarm 1 and Alarm 2 hysteresis (from 0 to ±2.0 % full scale).
Dead Band:
Defines zero baseline (from 0 to ±5.0 % full scale). Default is ±2.0 %.
The second screen contains only the "Delay" parameter.
If FlameGard is selected from the sensor list, the setting menu changes to the following screen.
4.  Use control push buttons to:
Accept changes and leave menu
Do not accept changes and leave menu
Return to the System menu.
5.1.5
Modifying Channel Parameters
1. 
Enter into System menu (see 5.1   S
2.  Use control push buttons to select a channel number to modify and press [ENTER] to confirm.
The first of two configuration screens displays.
NOTE: Use [DOWN] to toggle between the two screens:
US
ystem Menu).
GasGard XL
5 Configuration
22