OPERATING AND MAINTENANCE MANUAL
SWITCHMATIC SERIES CONTROLLER
2. Press
repeatedly until you exit the ADVANCED MENU.
3. Identical setting of start and cut-in pressure on both units.
For optimum operation of the synchronisation, the difference between the start and stop
pressures must be at least 1 bar.
4. Press
to disable this unit. The display will indicate 'OFF'.
5. Press
again on both devices to activate synchronisation.
Note 4: After 10 cycles the unit configured as E01 will display pressure and the unit
configured as E02 will display amps.
13. PRESSURE SENSOR CALIBRATION
In case of a wrong reading of the sensor it can be recalibrated. To calibrate the sensor it is
necessary to have a pressure gauge installed. Follow the steps below:
ZERO CALIBRATION
1. Open the taps to have the installation depressurised.
2. Press the buttons
3. Press
to validate.
www.proindecsa.com / proindecsa@proindecsa.com
and
simultaneously until the display shows 0.0 flashing.