1
Install thermostat
Prestige/VisionPRO with RedLINK: Mount the thermostat and wire to C and
R terminals of the Equipment Interface Module (EIM), or to a separate 24 volt
transformer (not provided).
NOTE:
When the VisionPRO with RedLINK thermostat is used with the EIM, the
relays in the thermostat do not function.
2
Install equipment interface module
Use screws & anchors as appropriate for the mounting surface. Mount the EIM near
the HVAC equipment, or on the equipment itself.
NOTE:
If you install more than one thermostat
and EIM, the EIMs must be at least 2 feet
apart.
NOTE:
If you are installing discharge and
return air sensors, refer to the mounting
instructions in the Alerts and Delta T
Diagnostics Installation Instructions packed
with the Prestige IAQ kit.
If an EIM is mounted inside a metal cabinet, it is
recommended to use a THM4000R1000 Wireless
Adapter for extended wireless range. Mount the
Wireless Adapter outside the metal cabinet and
connect to the ABCD terminals at the EIM.
CO NN EC
TED
CO NN EC
T
2
CONVENTIONAL
C
S1
S1
K
W
RC
Y
R
G
U1
U1
W2
U2
Y2
U2
A
HEAT PUMP
MCR34049A
WIRELESS
ADAPTER
THM4000R
POWER
WIRELESS SETUP
CONNECTED
CONNECT
S1
S1
O/B
Y
G
AUX
-E
Y2
L/A
Strip 1/4"
insulation,
then insert
wires as
shown.
EIM
A
B
C
D