Troubleshooting
Problem
Water is escaping from the spring bonnet Diaphragm in valve insert is faulty
Too little or no water pressure
The outlet pressure set does not remain
constant
9
Spare Parts
For Spare Parts visit resideo.com
10 Accessories
For Accessories visit resideo.com
MU1H-1101GE23 R1123
GB
Cause
Shut-off valves upstream or downstream
from filter not fully open
Pressure reducing valve is not set to the
desired outlet pressure
Filter mesh dirty
Domestic water station not mounted in
the direction of flow
Filter mesh dirty
Valve insert, sealing ring or edge of
nozzle is contaminated or worn
Rising pressure on outlet (e.g. in boiler) Check check valve, safety group etc.
7
Remedy
Replace valve insert
Open the shut-off valves fully
Set outlet pressure
Reverse rinsing
Fit filter in flow direction (note direction of
arrow on housing)
Reverse rinsing
Replace valve insert