Descargar Imprimir esta página

Publicidad

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

No: 24731 – 12/22 rev. 2
Catalog Number • Numéro de Catalogue • Número de Catálogo: DW-100-24
Country of Origin: Made in China • Pays d'origine: Fabriqué en Chine • País de origen: Hecho en China
The DW-100-24 Dual Technology Low Voltage Wall Switch sensor combines advanced passive infrared (PIR) and ultrasonic
technologies into one unit. The combined technologies help to eliminate false triggering even in difficult applications.
Selectable operating modes allow the sensor to turn a load ON, and hold it ON as long as either or both technologies detect occupancy.
After no movement is detected for the selected time delay, the lights switch OFF. A "walk-through" mode can turn lights OFF after only 3
minutes, if no activity is detected after 30 seconds following an occupancy detection.
The DW-100-24 has one relay and one ON/OFF button. Pressing the button toggles the state of the relay. It also includes an isolated
relay. The relay follows the state of the sensor only and is not affected by the switch.
Additionally, the DW-100-24 contains a light level sensor. If adequate daylight is present, the sensor holds the load OFF until light levels
drop, even if the area is occupied. Users can override this function by pressing the ON/OFF button. See Light Level Adjustment.
NOTE: Shaded cells below indicate default operation and switch setting.
Turning ON the Load (ON Mode)
The DW-100-24 can be programmed for either Auto ON or Manual ON mode. In either mode, the load can be turned ON or OFF using
the ON/OFF button.
Manual ON
With the ON Mode DIP Switch in the ON position, the occupant must press the ON/OFF button to turn ON
the load. The sensor keeps the load ON until no motion is detected for the selected time delay. There is a 30
DIP#8 ON
second re-trigger delay. If occupancy is re-triggers during the delay (see Trigger Mode), the sensor turns the
load back ON. After the re-trigger delay elapses the ON/OFF button must be pressed to turn ON the load.
Auto ON
With the ON Mode DIP Switch in the OFF position, the load turns ON and OFF automatically based on
occupancy. If the load is turned OFF manually, Presentation Mode operation applies. This prevents the load
DIP#8 OFF
from turning ON automatically after it was deliberately turned OFF. Pressing the button to turn lights ON
returns the sensor to Auto ON mode.
Presentation Mode
This is a feature of the Auto ON mode. When the relay is manually turned OFF the DW holds the lights OFF until no motion has been
detected for the duration of the Time Delay. With subsequent occupancy, the DW turns the load ON.
Time Delays
The DW-100-24 holds the load ON until no motion is detected for the selected time delay. Select the time delay using DIP Switch
settings. In the DW-100-24, both relays use the same delay.
Test/20 min
(DIP#1 & 2 OFF)
Time Delay
(15 min. DIP 1 ON & 2 OFF)
Wattstopper
Dual Technology Low Voltage Wall Switch Occupancy Sensor (V3)
Double technologie détecteur de présence d'interrupteur mural basse tension (V3)
Doble tecnología sensor de ocupación del interruptor de pared de bajo voltaje (V3)
Installation Instructions • Instructions d'Installation • Instrucciones de Instalación
DESCRIPTION AND OPERATION
A Test Mode with a short time delay of five seconds is set when DIP Switches 1 & 2 are OFF. It
cancels automatically after ten minutes, or when you set a fixed time delay. When the Test Mode
times out, the sensor will assume a 20 minute time delay. To restart Test Mode, change the time delay
setting to any fixed amount and then return it to the Test setting.
Time delays of 5, 15 (default), or 30 minutes are available. See DIP SWITCH SETTINGS for
information.
®
SPECIFICATIONS
Voltage .....................18-24VDC, 24VAC or Half-wave rectified AC
Current Consumption .......................................................... 35mA
Power Supply ...................................... Wattstopper Power Packs
Isolated Relay Rating ....................................... 1A @30VDC/VAC
Time Delay Adjustment ........................................ 5 to 30 minutes
Walk-Through Mode ...... 3 minutes if no activity after 30 sec.
Test Mode ............ 5 sec. for 10 min. with DIP Switch setting
PIR Adjustment ........................................ High or Low (DIP Switch)
Ultrasonic Adjustment .............. Minimum to Maximum (trimpot), Off
Frequency ..................................................................... 40kHz
Light Level Adjustment ............................................... 8fc to 180+fc
Alerts ................................................................... Selectable Audible
US Patent: 6617560

Publicidad

loading

Resumen de contenidos para LEGRAND Wattstopper DW-100-24

  • Página 1 Wattstopper ® Dual Technology Low Voltage Wall Switch Occupancy Sensor (V3) Double technologie détecteur de présence d’interrupteur mural basse tension (V3) Doble tecnología sensor de ocupación del interruptor de pared de bajo voltaje (V3) No: 24731 – 12/22 rev. 2 Installation Instructions •...
  • Página 2 Walk-Through The Walk-Through mode shortens the time delay to reduce the amount of time the load is ON after a brief moment of occupancy, such as returning to an office to pick up a forgotten item then immediately exiting. Walk-Through Mode The DW sensor turns the load OFF three minutes after the area is initially occupied, if no motion is detected after the first 30 seconds.
  • Página 3 INSTALLATION 1. Install the power pack according to its instructions. WARNING: TURN THE POWER OFF AT 2. Connect the power pack wires to the sensor as follows: THE CIRCUIT BREAKER BEFORE WIRING. RED wire (+24VDC) to the +24V IN terminal on the sensor. BLACK wire (Return) to common (COMM.) terminal on the sensor.
  • Página 4 Reset to Default Use the DIP Switch Settings tables on the previous page to return features to factory settings. To reset the DW press and hold the ON/OFF button for 10 seconds, until a triple beep sounds. This resets the sensor and disables light level control (the brightest ambient light will not hold the light OFF).
  • Página 5 INSTRUCTIONS EN FRANÇAIS DESCRIPTION ET FONCTIONNEMENT SPÉCIFICATIONS Le détecteur d’interrupteur mural basse tension à DW-100-24 double Tensions : ...8–24 VCC, 244VCA ou courant alternatif redressé technologie allient les technologies de l’infrarouge passif (IRP) et des ................mono alternance ultrasons en une seule unité. Les technologies combinées permettent Consommation de courant ...........
  • Página 6 Mode passage Le mode passage raccourcit le délai de temporisation pour réduire le temps d’ACTIVATION de la charge après un court moment de présence, comme, par exemple, une personne qui revient à son bureau pour prendre un objet qu’elle a oublié et qui repart immédiatement.
  • Página 7 INSTALLATION 1. Installez le bloc d’alimentation conformément à ses instructions. AVERTISSEMENT : COUPER LE 2. Connectez les fils du bloc d’alimentation au détecteur comme suit : COURANT AU DISJONCTEUR PRINCIPAL • Fil ROUGE (+ 24 VCC) du bloc d’alimentation à la borne + 24 V du AVANT D’INSTALLER LE CÂBLAGE.
  • Página 8 Pour désactiver le contrôle du niveau de luminosité, maintenez enfoncé le bouton MARCHE/ARRÊT du relais 1 pendant 7secondes, jusqu’à l’émission d’un double bip sonore. Réinitialisation sur les réglages par défaut Utilisez les tableaux de réglages de l’interrupteur DIP à la page précédente pour réinitialiser sur les réglages par défaut. Pour réinitialiser le DW, maintenez enfoncé...
  • Página 9 INSTRUCCIONES EN ESPAÑOL DESCRIPCIÓN Y FUNCIONAMIENTO ESPECIFICACIONES El sensor DW-100-24 del interruptor de pared con Voltajes: ......18–24 VCC, 24 VCA o rectificada de media onda tecnología doble combina las tecnologías infrarroja pasiva Consumo de corriente ................35ma (PIR) avanzada y la ultrasónica en una sola unidad. Estas Suministro de energía ......Paquetes de alimentación Wattstopper tecnologías combinadas ayudan a eliminar las falsas Especificaciones de relé...
  • Página 10 Modo de recorrido El modo de recorrido acorta el tiempo de demora para reducir la cantidad de tiempo en que la carga está encendida después de un breve momento de ocupación como, por ejemplo, volver a la oficina para buscar algo que se olvidó y salir inmediatamente. Modo de recorrido El sensor DW apaga la carga 3 minutos después que el área esté...
  • Página 11 INSTRUCCIONES DE CABLEADO 1. Instale la fuente de alimentación de acuerdo con sus instrucciones. ADVERTENCIA: DESCONECTE LA 2. Conecte los cables de la fuente de alimentación al sensor de la siguiente ALIMENTACIÓN EN EL DISYUNTOR manera: ANTES DEL CABLEADO. • Cable ROJO (+24 V CC) del paquete de alimentación a la terminal de +24 V del sensor.
  • Página 12 No. 24731 – 12/22 rev. 2 © Copyright 2022 Legrand All Rights Reserved. © Copyright 2022 Tous droits réservés Legrand. 800.879.8585 © Copyright 2022 Legrand Todos los derechos reservados. www.legrand.us/wattstopper...