COMM NDS MENU
– The commands menu permits the execution of occasional operations such as resetting measurements, meters, counter, etc.
– If the dvanced-level password has been entered, the commands menu can also be used to perform some automatic operations that are useful for configuring the instrument.
– The following table lists indicates the functions available in the commands menu, divided by access level required.
CODE
COMM ND
C.01
RESET HI-LO
C.02
RESET M X DEM ND
C.03
RESET P RTI L ENERGY METERS
C.04
RESET P RTI L HOUR COUNTER
C.06
RESET T RIFFS
C.07
RESET L RMS
C.08
RESET LIMITS
C.12
RESET TOT L HOUR COUNTERS
C.13
P R METERS TO DEF ULT
C.14
P R METER B CKUP
C.15
P R METERS RESTORE
C.16

WIRING TEST

– Once the required command has been selected, press
– To cancel the command execution, press MENU.
– To quit the commands menu, press s and t simultaneously.
WIRING TEST
– The wiring test permits verification of the correct installation of the energy meter.
– In order to run the test, the energy meter must be connected to an active system with the following conditions:
• Three-phase system with all phases present (V > 187V C PH-N)
• Minimum current flow in each phase > 1% of the CT full scale set
• Positive flow of energies (i.e. a normal system where the inductive load draws power from the supply).
– To launch the test execution, enter the commands menu and select command C.16, according to the instructions in the Commands Menu section.
– The test allows to verify the following points:
• Reading of the three voltages
• Phase sequence
• Voltage unbalance
• Reverse polarity of one or more CTs
• Mismatch between voltage/current phases
– If the test does not succeeds, the display shows the reason of the failure.
WIRING DI GR M
NOTES
1. Recommended fuses: F1 (fast).
2. The S2 terminals are connected to each other internally.
12
CCESS LEVEL
User / dvanced
User / dvanced
User / dvanced
User / dvanced
User / dvanced
User / dvanced
User / dvanced
dvanced
dvanced
dvanced
dvanced
dvanced
to execute it. The device will prompt for a confirmation. Pressing
L1
L2
L3
N
METER
T1
T2
Tariff input
100...240V~
DESCRIPTION
Resets the HI and LO values of all measurements
Resets Max Demand values for all measurements
Resets partial energy meters
Resets partial hour counters
Resets energy meters with tariff 1 and 2
Resets alarms with latch
Resets limit thresholds with latch
Resets total hour counters
Restores all settings to factory default values
Saves a backup copy of all setup parameters
Reloads the settings from the backup copy
Runs the test to check that the DME D330MID is connected correctly - See wiring test
again will execute the command.