ACC Acceleration time: Adjustment from 1 to 3 seconds, this
is the time during which the output voltage reaches 100%,
following a run command.
TORQ Starting torque: Adjustment from 10% to 25% of
maximum torque. This is the torque with which the motor will
begin acceleration.
If IMAX current limit is present: Adjustment from 50% to
200% of rated current.This is the maximum current value
admit during acceleration.When the set value is reached, the
acceleration ramp locks, thereby increasing its duration.
If the time exceeds 3 seconds, operation locks and FAULT is
indicated.
THE TRIMMERS ARE EQUIPPED WITH PINS IN ORDER TO FACILITATE ADJUSTMENT, WITHOUT
THE USE OF TOOLS. AT THE END OF THE START-UP OF THE DEVICE, YOU CAN REMOVE THEM
TO AVOID LATER INAPPROPIATE CHANGES.
•
Checking for the presence of input phases before carrying out start-up.
•
Checking for the presence of the motor before carrying out start-up.
•
Checking of correct operation of the SCRs.
•
Checking the maximum current during start-up
(only in version with current monitoring).
REV. 1 Printed 02/2020
ADJUSTMENT
INDICATORS
LED INDICATORS
PWR FLASHING = Logic board power supply present.
RUN ON= RUN command active.
END ON = Start-up completed, remains active during the
run and switches off 0.5 seconds after the stop: contact
3-4 closed and contact 4-5 open.
FLASHING FAULT= FAULT flashing, see
troubleshooting
page 14.