SMS Hstart SSW105 Manual De Uso página 14

Arrancador suave trifásico
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

SMS-Hstart
Diagnostics
The POWER led
doesn't flash
The RUN doesn't
lit
The FAULT* LED
flashes once
The FAULT* LED
flashes three
times
The FAULT* LED
flashes four times
The FAULT* LED
flashes five times
The FAULT* LED
flashes six times
The FAULT* LED
flashes eight
times
The FAULT* LED
flashes nine times
The FAULT* LED
flashes ten times
* The FAULT LED flashes "xN" indicates that the FAULT LED flashes synchronously with the PWR LED "N" times.
14
TROUBLESHOOTING
Cause
The control board is not
powered
The starting current exceeds
the maximum limits of the
device
SMS-Hstart
is not
synchronizing with the mains
SMS-Hstart
doesn't detect
the 3 phases of the power
supply
SMS-Hstart
recognises an
incorrectly connected motor
SMS-Hstart
detects
the failure of a power
component
SMS-Hstart
detects an
overload on the power
components
SMS-Hstart
is not able to
finish the start-up process
SMS Start detects an
undesired ignition
SMS-Hstart
Checks
Check that the correct supply is
present on terminals L1/L2/L3
Check that between terminals
1-2 (RUN) the contact il closed
Check the insulation of the
motor. Make sure that the size of
the device is compatible with the
power of the motor
Check that the mains frequency
is between 45Hz and 65Hz
Check that the motor
is properly connected.
Check that the correct supply is
present on terminals L1/L2/L3
Check that the motor is properly
connected
Make sure that the power supply
voltage is correct
Make sure that the size of the
device is compatible with the
power of the motor. Wait a few
minutes and try to start it again
Try to increase again
the IMAX trimmer
Try to increase again
the TORQ trimmer
CODE FORMAT
Conclusions / Actions to be
performed if the suggested
checks are negative
Probable damage on the
internal supplier. Contact SMS
Probable failure of the run
command. Contact SMS
Rotate the "ACC" trimmer
at the maximum value and
"TORQ" at the minimum.
Contact SMS
Probable electrical network
failures or faulty components
Probable damage on the
power components.
One of the phases missing
Probable damage on the
power components
Probable damage on the
power components
Replace the device with a
greater size one
Replace the device with a
greater size one
Probable damage on the
power components
REV. 1 Printed 02/2020