Danby DAS180DBAHWDB Guia De Instalacion página 24

Aire acondicionado dividido
Ocultar thumbs Ver también para DAS180DBAHWDB:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

INSTALLATION INSTRUCTIONS
Step 4: Connect pipes
When connecting refrigerant pipes, be careful not to use excessive torque or
to deform the piping in any way. Connect the low pressure pipe fi rst and then
connect the high pressure pipe.
Note: When bending connective refrigerant piping, the minimum bending radius
is 10 cm (3.9 in).
CONNECTING PIPING TO INDOOR UNIT
1. Align the center of the two pipes that will be connected.
2. Tighten the fl are nut as tightly as possible by hand.
3. Using a spanner, grip the nut on the unit tubing.
4. While fi rmly gripping the nut on the unit tubing, use a torque wrench to tighten the fl are nut according
to the torque values in the torque requirements table below. Loosen the fl aring nut slightly, then tighten
again.
Outer Diameter of Pipe (mm)
Ø 6.35 (Ø 0.25 in)
Ø 9.52 (Ø 0.375 in)
Ø 12.7 (Ø 0.5 in)
Ø 16 (Ø 0.63 in)
TORQUE REQUIREMENTS
Tightening Torque (N•cm)
1,500 (11 lb•ft)
2,500 (18.4 lb•ft)
3,500 (25.8 lb•ft)
4,500 (19 lb•ft)
23
Excessive force can break the nut or
damage the refrigerant piping. Do not
exceed the torque requirements shown
in the table below.
Add. Tightening Torque (N•m)
1,600 (11.8 lb•ft)
2,600 (19.18 lb•ft)
3,600 (26.55 lb•ft)
4,700 (34.67 lb•ft)