FAULTS

During troubleshooting, make sure
that the mains voltage is switched on
and the gas supply is open.
Remove the bottom part of the
outside housing (GA42) and the
upper part of the outside housing (GA
60/85/110) for maintenance on the
internal parts.
6.1

Troubleshooting table

/i
Fault
The heater does not
1
start up.
2
3
4
5
6
The heater triggers a
7
fault; the red lamp on
the operating panel
lights up.
8
2
2
22
Cause
The heater has no volt-
age.
The fan motor runs
heavily or is blocked.
The thermostat is set to
a too low temperature.
There is no through-
connector on the ther-
mostat connection.
Defect in the operating
panel
Filter at the differential
pressure switch
is clogged.
The mains plug has
been incorrectly inserted
into the socket.
The earth of the socket
is not OK.
4
0
0 .
2
0
9 .
4
7
-
e r
. v
0
4
40.020.947 - rev 05 - 2016
Warning
Remove the mains plug from the
socket and shut off the gas supply
during repair.
Solution
Check the electrical connec-
tion.
Check if the fan motor is dirty
or blocked.
Replace the fan motor.
Correct the settings.
Fit the through-connector.
Repair or replace the operat-
ing panel
Replace filter.
Reverse the plug.
Have the earth of the socket
check by a recognised
installer.
-
2
0
1 1
GA 24-42-60-85-110
G
ENGLISH
Action
User
User
Dealer
User
User
Dealer
User
User
User
A
4
2
6 -
0
8 -
- 5
1 1
0