Electrical Installation; Troubleshooting - Siemens RLE127 Instrucciones De Montaje

Regulador de temperatura diferencial
Ocultar thumbs Ver también para RLE127:
Tabla de contenido

Publicidad

3.
Fit protection pocket in the pipe. If required, use
sealing material (hemp, Teflon tape, or similar).
4.
Insert controller into the protection pocket and snap
it on.
5.
Fill piping system again.
6.
Mount external temperature sensor according to the
Mounting Instructions supplied with it.

Electrical installation

• Ensure that the local regulations for electrical installa-
tions are complied with
• The connecting terminals are located under the flexi-
ble plastic cover
• Make wiring according to the plant documentation. If
not available, use the connection diagrams contained
in these Installation Instructions
• Observe the permissible cable lengths
• Switch on power only when commissioning the con-
troller
Settings
3
2
1
1
LED for test mode / fault / normal operation
2
DIP switch block
3
Setting slider for minimum charging temperature
4
Potentiometer for loading temperature (40...90 °C)
5
Potentiometer for maximum temperature (40...130 °C)
Switching differential:
Where?
What?
DIP switch block,
1
2
switches no. 1 and 2
Operating mode (B2):
DIP switch block,
3
switch no. 3
Application type (B3):
DIP switch block,
4
5
switches no. 4 and 5
Test mode:
DIP switch block,
6
switch no. 6
Frost protection function:
DIP switch block,
7
switch no. 7
Siemens Building Technologies
4
5
Switching differential = 8 K
Switching differential = 1 K
Switching differential = 4 K
Switching differential = 2 K
With minimum charging temperature
Without minimum charging temperature
Applications 6, 7
2 Exchangers (∆t)
Application 5
2 Collectors (∆t)
Applications 3, 4
Bypass (°C)
Applications 1, 2
Standard
Test mode
Normal operation
Frost protection ON
Frost protection OFF
CE1G3337xx
Setpoint (1...30 K):
Temperature
Temperature differential required between the two
setting slider
plant elements
Minimum charging temperature (30...80 °C):
Setting slider 3
When switch no. 3 is set to
Absolute (load) temperature (40...90 °C):
Switches no. 4 and 5 are set
Potentiometer 4
to
Maximum temperature (40...130 °C):
Potentiometer 5
Switches no. 4 and 5 are set to
Indication of operating state
The red LED indicates the controller's operating state:
• LED lit: Mains voltage present (normal operation)
• LED flashes fast (4 Hz): In test mode
• LED flashes slow (1 Hz): Fault (B2)
The LED is also visible when the cover is fitted.
Commissioning
1.
Remove housing cover.
2.
Lift flexible plastic cover so that you can access the
setting elements.
3.
Make the settings:
Switching differential (switches no. 1 and 2)
Operating mode (with / without minimum charging
temperature, switch no. 3)
Application type (switches no. 4 and 5)
Test mode (switch no. 6 =
Frost protection (switch no. 7 =
4.
Replace flexible plastic cover.
5.
Switch power on. LED for the operating state must
flash (test mode).
6.
Move temperature setting slider to the minimum
value (<5 K) to prove contact Q1–Q3
► If response is wrong, refer to "Troubleshooting"
7.
Move temperature setting slider to the maximum
value (>25 K) to prove contact Q4–Q6.
► If response is wrong, refer to "Troubleshooting"
8.
Switch power off.
9.
Switch controller back to normal operation (set
switch no. 6 to
OFF).
10. Switch power on. LED for the operating state must
light up (normal operation).
11. If a remote setting unit is used, set the controller's
temperature setting slider to EXT.
12. First, set temperature setting slider to the minimum
value, then to the maximum value: Observe the con-
trol. The response may neither be too fast nor too
slow.
► If response is wrong, refer to "Troubleshooting"
13. Adjust the setpoint with the temperature setting
slider.
14. Replace housing cover.

Troubleshooting

Wrong response
Possible causes
Regulating units do
• Regulating units not con-
not respond
• No power supply
07.01.2008
or
ON)
ON,
OFF)
nected
3/16

Publicidad

Tabla de contenido
loading

Tabla de contenido