TROUBLESHOOTING
Problem
No AC output is available, but
generator is running.
Cause
I.
One of the circuit breakers is
open.
2.
Fault in generator.
3.
Poor connection
or defective
cord set.
4.
Connected
device is bad.
Correction
I.
Reset circuit breaker.
2.
Contact Authorized service
facility.
3.
Check and repair.
4.
Connect another device that is in
good condition.
I.
Short circuit in a connected
load.
I.
Disconnect
shorted electrical
Generator
runs good at no-load
load.
but "bogs"
down" when
loads are
2.
Generator
is overloaded.
2.
See "Don't
Overload
Generator".
connected.
3.
Shorted generator
circuit.
3.
Contact Authorized
service
facility.
I.
Failed battery.
I.
Replace battery.
Generator
will not start; or starts
2.
Low oil level.
2.
Fill crankcase to proper level or
and runs rough,
place generator
on level surface.
I.
Out of gasoline.
I.
Fill fuel tank.
Generator
shuts down during
operation.
2.
Low oil level.
2.
Fill crankcase to proper level or
place generator
on level surface.
Generator
lacks power.
Load is too high.
See "Don't
Overload
Generator".