Grounding The Generator; Use Of Extension Cords - Porter Cable PCI2200 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

ASSEmBLY

GROUNDING ThE GENERATOR

A grounding nut (X, Fig. 3) is supplied
with the generator for use when required
by local electrical ordinances. Your
local electric company or a certified
electrician should be able to help you
with this information.

USE OF ExTENSION CORDS

WARNING: Use only grounded
extension cords. Use only three wire or
double-insulated power tools.
Only use grounded extension cords
that are rated for outdoor use and
equipment with a third-wire ground. It
is recommended that GFCI protected
spider box or inline GFCI adapter are
used when connecting to any of the
generator's receptacles.
Volts
120V
240V
Ampere
AWG
Rating
0–10
10–13
13–16
16–25
25–30
Extension Cord
Length
25 Foot
7.6 m
50 Foot
15.2 m
minimum gauge for Extension Cord Sets
Total Length of Cord in Feet
0–25
26–50
(7.9–15.2 m)
(0–6.7 m)
0–50
51–100
(0–15.2 m)
(15.5–30.5 m)
16
16
14
12
10
Amp
Voltage Drop
Load
16 AWG 14 AWG
10 A
15 A
20 A
30 A
10 A
15 A
20 A
30 A
When a long extension cord is used
to connect an appliance or tool to the
generator, a voltage drop occurs. The
longer the cord, the greater the voltage
drop. This results in less voltage being
supplied to the appliance or tool and
increases the amount of current (amp)
draw or reduces performance. A heavier
cord with a larger wire size will reduce
the voltage drop. Be sure to choose a
cord that will supply enough voltage
to operate your tool or appliance. The
tables indicate appropriate gauge for
extension cords and the voltage drop
caused by the use of extension cords,
given different electrical loads.
CAUTION: Operating equipment at
low voltage can cause it to overheat.
Using an excessively long extension cord
can cause the cord to overheat.
WARNING: Keep electrical cords in
good condition. Do not use worn, bare
or frayed cords because they can cause
electrical shock.
51–100
(15.5–30.5 m)
101–200
(30.8–60.9 m)
16
14
16
14
14
12
12
12
10
10
2.0
1.3
3.0
1.9
4.0
2.5
6.0
3.8
4.0
2.5
6.0
3.8
8.0
5.0
12.0
7.5
18- ENG
101–150
(30.8–45.7 m)
201–300
(61.2–91.4 m)
14
12
12
10
Not
Recommended
12 AWG
10 AWG
0.8
0.5
1.2
0.8
1.6
1.1
2.3
1.6
1.6
1.1
2.3
1.6
3.1
2.1
4.7
3.2

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Pci2800Pci5000

Tabla de contenido