Parker Hiross Hypercool ADS000 Manual De Uso página 5

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 9
6. Maintenance
Before accessing live electrical parts , disconnect the power supply
to the unit using disconnect switch QS.
Maintenance must only be performed by specialist personnel.
N.B.: Always use original spares supplied by the manufacturer.
Failure to do so renders the manufacturer not liable for incorrect
unit operation.
Maintenance program
COOLING COIL
Verify the state of the coil; if necessary clean it as follows:
• in spring: clean using a vacuum cleaner (or compressed air).
• in summer: this being the hottest period, keep the coil as
clean as possible, with a vacuum cleaner (or compressed air)
and, if necessary, with water.
• in winter: clean with water (with the fan off ).
• if necessary (coil blocked) remove the fan and clean the coil
in the opposite direction to the air fl ow using a high pressure
water jet (this operationmust be performed by a technician
to avoid damage).
Check that the fan rotates freely without any abnormal noise.
Also check the current absorption.
(Th e fan's sealed lubricating system needs no maintenance).
COMPRESSED AIR CIRCUIT
If the air compressor consumes signifi cant quantities of oil, pe-
riodically wash the tubing as follows:
Disconnect the air inlet and outlet. Force a chlorinated solvent
(which must be neither strongly acid or alkaline) through the air
tubing with a centrifugal pump to remove the carbon deposits
(ensure the tubing is perfectly dry and free from solvent vapour
before reassembling).
English
FAN (S)
7. Dismantling
Th e heat exchanger does not contain any fl uids that are harmful
for the environment. When disposing of materials or recycling
them, refer to the laws in force in the country of use.
%
structural work
pipes/headers
electrical cables
8. Spare parts list (see Fig. 5)
It is recommended the use of original spare parts.
When placing an order quote the part's code, as well as the unit's
model no. and serial no.
ADS/ADT/ADW
Recycling Disposal
steel/epoxy-polyester resins
copper/aluminium/carbon steel
copper/PVC
3