Mounting / Installation
• Remove cable sheathing over a sufficient length (corresponding to length of terminals). Fit screwed gland
(1), thrust ring (2) and seal (3) over cable and insert in threaded hole.
IMPORTANT
Tie up strands at a distance of 30 mm from terminals using cable clips! Strands with
supply voltage may not come into contact with low voltage terminals when coming loose
in case of defect!
• Screw in screwed gland and firmly tighten with WAF 19 spanner. Shorten stranded wires to the exact
overall length, then strip approx. 7 mm insulation and connect to terminals corresponding to the
electrical connection diagram.
• Core sleeves may be used for the stranded wires. If too many threaded holes are punched out, they can
be closed off again with the dummy washers (4) supplied with the device.
• If the controller features an SN6 input (corresponding to identity code), the corresponding input socket
is located in the rear row on the left side in a M20 x 1.5 threaded hole. Any ProMinent cable
combination coax SN6 can be connected to this input.
Packing list, cable screwed glands
5x screwed gland
5x thrust ring
5x seal
3x seal
3x seal
2x seal
5x seal
2x seal
3x dummy washer
Additionally for expansion version
4x screwed gland
4x lock nut
The four additional cut-outs in the front row can be used for M12 x 1.5 screwed glands. All commercially
available M12 x 1.5 screwed glands (suitable for type of enclosure IP 65) with lock nut (brass, galvanised,
nickel-plated) can be used as cable screw fittings.
Available from ProMinent under:
1x cable screwed gland M12 x 1.5, black
1x lock nut M12 x 1.5 brass, nickel-plated
• Fit lock nut M12 x 1.5 (6) on the inside and mount M12 x 1.5 screwed gland (5) from outside and firmly
tighten (WAF 15).
Electrical connection for control panel installation
Normally, only the rear row of threaded holes should be used on devices mounted in a control panel. The
front row (M12 x 1.5 cut-outs) are located outside the control panel. The cable screw fittings supplied with
the device are not required for control panel installation. In this case, the individual stranded wires
(without pull-relief and seal) are routed directly through the holes and connected to terminals
corresponding to the electrical connection diagram. The holes are broken out as described under Point
4.3.1.
M20 x 1.5
M20 x 1.5
M12 x 1.5
M12 x 1.5 brass, nickel-plated
Item (1)
Item (2)
Item (3)
Item (3)
Item (3)
Item (3)
Item (3)
Item (3)
Item (4)
Item (5)
Item (6)
Part No. 1009734
Part No. 1018314
29