Filling The Installation - CLIMAVENETA MICS-C FF Serie Manual De Instalación-Operación-Servicio

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

Connections made by
manufacturer
13
9
14
1
8
13
12
10
7
Installations containing antifreeze or covered
by specifi c legislation must be fi tted with hydraulic
disconnectors.
The manufacturer is not liable for obstruction,
breakage or noise resulting from the failure to
install fi lters or vibration dampers.
SIZE AND POSITION OF CONNECTIONS
Size
A (mm)
B (mm)
C (mm)
Hydraulic connections (Ø)
PH
Electrical conductivity
Chlorine ions
Sulphuric acid ions
Total iron
Alkalinity M
Total hardness
Sulphur ions
Ammonia ions
Silicon ions

FILLING THE INSTALLATION

Remove the inspection panel.
Before fi lling, check that the installation drain valve
is closed.
Open all installation, appliance and terminal air
vents.
Open the gate valves.
Begin fi lling, slowly opening the water fi lling cock in-
side the unit.
When water begins to leak out of the terminal air
vent valves, close them and continue fi lling until the
pressure gauge indicates a pressure of 1.5 bar.
Replace the inspection panel.
MICS-C / MICS-CN
Connections to be made
by fi tter
16
1
2
4
15
1
2
11
15
6-8
less than 200 mV/cm (25°C)
less than 50 ppm
less than 50 ppm
less than 0,3 ppm
less than 50 ppm
less than 50 ppm
none
none
less than 30 ppm
5
6
SYSTEM WATER OUTLET
T
F
3
6
T
SYSTEM WATER INLET
Particular types of water used for fi lling or top-
ping up must be treated with appropriate treatment
systems. For reference values, see the table.
0072
100
226,5
63
G1-1/4
The installation must be fi lled to a pressure of
between 1 and 2 bar.
It is recommended that this operation be repea-
ted after the unit has been operating for a number
of hours. The pressure of the installation should be
checked regularly and if it drops below 1 bar, the
water content should be topped-up.
Check the hydraulic tightness of joints.
1 Pressure gauge
2 Vibration damper joint
3 Gate valve
4 Calibrating valve
5 Flow switch
6 Thermometer
7 Pump
8 Safety valve
9 Air vent
10 Expansion tank
11 Mesh fi lter
12 Fill/top-up
13 Temperature sensor
14 Differential pressure switch
15 Drain/chemical washing valve
16 Plate heat exchanger
0092
0122
100
260
226,5
363
63
63
G1-1/4
G1-1/4
WATER INLET
WATER OUTLET
English 06/09
7

Publicidad

Tabla de contenido
loading

Tabla de contenido