PLUG N' GO OPERATION (PNG)
All loads in the local DLM network that are CCT compatible will automatically respond to schedule events in the LMTS-101-CCT.
Additionally, all loads in the local DLM network will respond to the On/Off button whether or not they are CCT compatible.
NOTE: Only loads bound to the LMTS-101-CCT button will respond to the schedule events. See the following section on Push 'n Learn.
PUSH N' LEARN
Load Selection Procedure
A configuration button allows access to our patented Push n' Learn™ technology to change the binding relationship between switch
buttons and loads.
Step 1 Enter Push n' Learn
Using a pointed tool, press and hold the configuration button for 3 seconds, until the Red LED on the switch begins to blink.
When you release the switch's configuration button, the red LED on other communicating DLM Local Network devices begins to blink.
The DLM Local Network is now in PnL mode. The Red LEDs continue to blink until you exit PnL mode.
All loads in the room turn OFF after entering PnL. After one second, one load turns ON. This is Load #1, which is bound to the button as part
of the Plug n' Go factory default setting. The Blue LED will be ON for all switch buttons and sensors that are bound to this load.
Step 2 Load selection
Press and release the configuration button to step through the loads connected to the DLM Local Network. As each load turns ON note
which devices (switch buttons and sensors) are showing the blue LED. These devices are currently bound to the load that is ON. By
default, all loads in the local DLM network are bound to the LMTS-101-CCT.
To unbind a switch button from a load, press the switch button while its blue LED is ON. The blue LED turns OFF to indicate the button
no longer controls the load that is currently ON. Note that if LMTS-101-CCT button is unbound from the load, the schedule events will
also have no effect on that load.
Pressing the switch button again while the load is ON rebinds the load to the button and the blue LED illuminates.
Additional Push 'n Learn Features
Three parameters are displayed in the screen while in Push 'n Learn mode. For details on these parameters, see the Push 'n Learn
section on page 4.
Step 3 Exit Push n' Learn
Press and hold the configuration button until the red LED turns off, approximately 3 seconds.
ACCESSING PROGRAMMING PARAMETERS
To access programmable parameters directly on the LMTS-101-CCT, remove the switch
button to expose the Select and navigational buttons behind it.
Removing the Switch Button
Insert a small flat edged screwdriver between the button and the frame, at the bottom of
the button. Rotate the screwdriver downward so that it catches the channel in the button
and keep pressing down till the button is released and springs forward.
Replacing the Switch Button
Reinsert the lens in the proper orientation: place the two posts at the top of the button at
a 30 degree angle, with the chamfered edge facing up. Gently press the bottom of the
button until it locks in place.