67. Temperature unit
CELC Displays the temperature in °C.
FAHR Displays the temperature in °F.
Default
CELC
_______________________________________________________________
68. Temperature coefficient
This is the percentage the battery capacity changes with temperature, when temperature
decreases to less than 20°C (above 20°C the influence of temperature on capacity is
relatively low and is not taken into account). The unit of this value is "%cap/°C" or percent
capacity per degree Celsius. The typical value (below 20°C) is 1%cap/°C for lead acid
batteries, and 0,5%cap/°C for Lithium Iron Phosphate batteries.
Default
0%cap/°C
_______________________________________________________________
69. Aux input
Sets the function of the auxiliary input:
START Auxiliary voltage, e.g. a starter battery.
MID Mid-point voltage.
TEMP Battery temperature.
The cable with integrated temperature sensor has to be purchased separately (part no:
ASS000100000). This temperature sensor is not interchangeable with other Victron
temperature sensors, as provided with Multis or battery chargers.
4.3 History data
The BMV tracks several parameters regarding the state of the battery
which can be used to evaluate usage patterns and battery health.
Enter history data by pressing the SELECT button when in normal mode.
Press + or – to browse the various parameters.
Press SELECT again to stop scrolling and show the value.
Press + or – to browse the various values.
Press SELECT again to leave the historical menu and go back to normal
operation mode.
The history data is stored in non-volatile memory, and will not be lost when
the power supply to the BMV is interrupted.
Range
CELC/FAHR
Range
0 – 2%cap/°C
Step size
0,1%cap/°C
27