3-6. Operating Mode Description

Operating
Description
mode
When the input voltage is within
acceptable range, UPS will provide
Online mode
pure and stable AC power to output.
The UPS will also charge the battery at
online mode.
When the input voltage is within
ECO mode
setting range (±3%Vo max), UPS will
(Efficiency
bypass voltage to output for energy
Corrective
saving. PFC and INVERTER are still
Optimizer)
active at this mode.
When the input voltage is within
AECO mode
(Advanced
setting range (±3%Vo max), UPS will
Efficiency
bypass voltage to output for energy
Corrective
saving. PFC and INVERTER are off at
Optimizer)
this mode.
When input frequency is within 40 Hz
Frequency
to 70 Hz, the UPS can be set at a
Converter
constant output frequency, 50 Hz or
mode
60 Hz. The UPS will still charge
(Rack)
battery under this mode.
When the input voltage is beyond the
Battery
acceptable range or power failure and
mode
alarm is sounding every 4 second,
UPS will backup power from battery.
When input voltage is within
acceptable range but UPS is
Bypass
overload, UPS will enter bypass mode
mode
or bypass mode can be set by front
panel. Alarm is sounding every 10
second.