KEB COMBIVERT F5 Manual De Instrucciones página 32

Tamaño d
Ocultar thumbs Ver también para COMBIVERT F5:
Tabla de contenido

Publicidad

Anexo B
• "D Housing - Series Combivert, Cat. Nos. 07, 09, 10, 12, 13 or 14, followed by F5, followed
by B or C, followed by 0, 1, 2, 3, A, B, C or D, followed by D-, followed by four suffixes.
D Housing - Series Combivert, Cat. No. 07, 09, 10, 12, 13 or 14, followed by F5, followed
by B or C, followed by 0, 1, 2, 3, A, B, C or D, followed by D-, followed by three suffixes
and followed by 4 or E or J.
Motor Overtemperature Protection:
above drive models are not provided with load and speed sensitive overload protection
and thermal memory retention up on shutdown or loss of power (for details see NEC, ar-
ticle 430.126(A)(1)".
For 240 V Models:
„Suitable For Use On A Circuit Capable Of Delivering Not More Than 10000 rms Symmetrical
Amperes, 240 Volts Maximum, when Protected by Fuses, see Instruction Manual for speci-
fied fuse details and alternate Branch Circuit Protection details."
For 480 V Models:
„Suitable For Use On A Circuit Capable Of Delivering Not More Than 10000 rms Symmetrical
Amperes, 480 Volts Maximum, when Protected by Fuses, see Instruction Manual for speci-
fied fuse details and alternate Branch Circuit Protection details."
For all Models:
Branch Circuit Protection:
Inverter
model
F5/F6
07
07
09
09
10
10
12
12
13
14
32
input fusing for inverters of Drive Series F5-D and F6-D:
Input
Voltage
Fuse class RK5 or J or CC
(V)
240 /1ph
240 /3ph
480 / 3ph
240 /1ph
240 /3ph
480 / 3ph
240 /1ph
240 /3ph
480 / 3ph
240 /1ph
240 /3ph
480 / 3ph
480 / 3ph
480 / 3ph
UL 248
[ A ] *
15
10
10
20
15
10
30
20
12
35
25
15
25
30
Semiconductor fuses
Cat. No.
(#)
50 140 06 40
50 140 06 20
50 140 06 12
50 140 06 40
50 140 06 25
50 140 06 12
50 140 06 63
50 140 06 35
50 140 06 16
50 140 06 100
50 140 06 50
50 140 06 25
50 140 06 40
50 140 06 40

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Combivert f6

Tabla de contenido