Anexo B
Inverter
#1) The voltage rating of the Class rated fuses shall be at least equal to the voltage rating
of the Drives.
Branch Circuit Protection: Type E Self Protected Manual Motor Controllers for
inverters F5–B housing. Type and manufacturer and electrical ratings as specified below:
Cat. No.
05F5
05F5
07F5
07F5
09F5
09F5
10F5
10F5
Cat. No.
05F5
05F5
07F5
07F5
09F5
09F5
10F5
10F5
12F5
Drive input rating
240V/ 1ph
240V/ 3ph
240V/ 1ph
240V/ 3ph
240V/ 1ph
240V/ 3ph
240V/ 1ph
240V/ 3ph
Drive Input
rating #
Input Voltage
[V]
240 /1ph
240 /3ph
480 / 3ph
240 /1ph
240 /3ph
480 / 3ph
240 /1ph
240 /3ph
480 / 3ph
240 /1ph
240 /3ph
480 / 3ph
480 / 3ph
Self Protected Manual Motor
Controller Type and manufac-
turer
PKZMO–10E, Eaton Industries
PKZMO-6.3E, Eaton Industries
PKZMO–16E, Eaton Industries
PKZMO–10E, Eaton Industries
PKZMO-20E, Eaton Industries
PKZMO–16E, Eaton Industries
PKZMO-32E, Eaton Industries
PKZMO–16E, Eaton Industries
Self Protected Manual Motor
Controller Type and manufac-
turer
UL248 Fuse Class CC, J
or RK5 #1)
[A]
10
6
5
15
10
6
20
15
10
30
25
12
15
Self Protected Ma-
nual Motor Controller
rating
230V/1ph, 1.5 hp
230V / 3ph, 1.5 hp
230V/1ph, 2 hp
240V/3ph, 3 hp
230V/1ph, 3 hp
230V/ 3ph, 5 hp
230V/1ph, 5 hp
230V/ 3ph, 5 hp
Self Protected Ma-
nual Motor Controller
rating
ES - 31