Repair Information - Eaton Greengate ControlKeeper 4 CK4-120NO Instrucciones De Instalación

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

until the STATUS LED turns OFF . Once the STATUS LED
turns OFF , release the reset button. The ControlKeeper 4
unit will be reset back to factory default settings.
Programming the ControlKeeper 4
The ControlKeeper 4 is programmed using Keeper
Enterprise Software. Please refer to the Keeper Enterprise
Manual for programming details. It is recommended that a
Clear Command be performed on the controller before the
first programming download to clear any test data that may
be left in the controller from factory testing.
Item Reference
The ControlKeeper 4 consists of a logic board with a clear
separation of line-voltage and low voltage components.
There are several features of note on the logic board as
pointed out in the below item reference diagram.
2
1
14
13
1.
Individual Relay Override Switches (Temporary override)
2.
System Status LEDs
3.
Relay Status LEDs
4.
Panel Hardware Override Switch (ALL OFF , AUTO, ALL
ON)
5.
Transformer Wiring Leads: White = Neutral,
Orange = 277V, Black = 120V
6.
Relay Wiring Terminals
ControlKeeper 4
3
4
Figure 12. Item Reference
12
11
10

Repair Information

If a repair becomes necessary on your ControlKeeper 4 unit,
please refer all service to Greengate's technical support line
at 1-800-553-3879. The ControlKeeper 4 contains no user
serviceable parts.
5
9
8
7
7 .
Panel Reset Switch
8.
Network Terminator Jumper
9.
Network Wiring Terminal Block
10. Digital Switch Port
11. Panel Communications Port
12. Peripheral Power Terminal: +24 VDC, DC Ground
13. Switch Input Wiring Channels
14. Panel Network Address DIP Switches
General Information