Installation Recommendations - Friedrich VERT-I-PAK A-Serie Manual De Instalación Y Operación

Ocultar thumbs Ver también para VERT-I-PAK A-Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Vert-I-Pak Installation Recommendations
For proper unit performance and maximum operating lifeplease refer to the minimum installation clearances
Figure 1
®
VERT-I-PAK
units must be installed on an outside wall. Confined spaces and/or covered areas should be
avoided. Units should be installed no closer than 12" apart when two units are side by side. If three or more
units are to operate next to one another allow a minimum of 60" between units or pairs of units. Also, a vertical
clearance of 60" should be maintained between units. Units installed on the bottom floor should be mounted at
least 6" off of the ground.
6"
SMALL RECESS OK
60"
60"
60"
6"
Figure 2
Any time obstructions are present use the
following guidelines for proper spacing
from the VERTI-I-PAK louver:
• For minor obstruction such as lamp
poles or small shrubbery a clearance of
24" from the outdoor louver should be
maintaned.
• For major obstructions such as a solid
fence, wall or other heat rejecting
device like a condensing unit, a
minimum distance of 72" should be
kept.
The above suggestions are for reference only and do not represent all possible installations. Please contact Friedrich Air Conditioning
(see contact information on back cover) for information regarding affects of other installation arrangements.
By following these simple recommendations you can be confident that your Friedrich Vert-I-Pack
free operation.
4
60"
60"
60"
60"
6"
OUTDOOR
CONDENSING
UNIT
B
A
LARGER RECESS OK. IF A> 5xB
BUILDING
60"
V
P
A
K
12"
POLE
MAJOR OBSTRUCTION
below.
60"
60"
60"
24"
V
P
A
K
SHRUB
FENCE
®
will provide years of worry-
60"
12"
V
P
A
K
24"
72"

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Vea09Vha09Vea12Vha12Vea18Vha18 ... Mostrar todo

Tabla de contenido