|
Jandy
®
JE Heat Pumps
Figure 1.
Jandy JE Heat Pumps Dimensions
MODEL SIZE
JE1500T
JE2000/2500T
JE3000T
3.5"
C
Equipment Pad
Place the heat pump on a flat slightly pitched surface,
such as a concrete or fabricated slab (pad). This allows
proper drainage of condensation and rain water from the
base of the unit. If possible, the pad should be placed at
the same level or slightly higher than the filter system
equipment pad.
NOTE Ensure that the pad is pitched not more than ¼
inch per foot cm per toward the compressor end
(front) of the heat pump. Pitch slab from back to
front ¼ inch per foot maximum and level from
side to side.
Condensation and Drainage
Condensation will occur from the evaporator coil while
the unit is running and drain at a steady rate, usually
3 to 5 gallons (11.4 to 18.9 liters) per hour, depending
upon ambient air temperature and humidity. The more
humid the ambient conditions, the more condensation
will be produced. Keep the drain holes of the base of the
unit clear of debris.
If the heat pump is installed indoors*, means of
condensate disposal must be provided
* Indoor installation requires factory consultation
Lawn Sprinklers
Keep lawn sprinkler heads from spraying on the heat
pump to prevent corrosion and damage. Use a deflector
if needed.
Installation and Operation Manual
A
33"
34"
36"
40"
36"
44"
A
B
8"
DIMENSIONS
B
C
D
12.5"
9"
13.8"
19"
13.8"
19"
D
E
Table 2. Heat Pump Clearances
Side of
Minimum Clearances for
Heat
pump
Inches
Front
24
Rear
12
Left
12
Right
12
Top
60
NOTE: Clearances listed in Table 2 are manufacturer's tested values.
These are given as minimum values. Where local and national codes
apply, and values are different than those listed in Table 2, use the
greater value to ensure safe and proper operation.
Roof Run-off
Make sure the heat pump is not located where large
amounts of water may run-off from a roof into the unit.
Sharp sloping roofs without gutters will allow massive
amounts of rain water, mixed with debris from the roof
to be forced through the unit. A gutter or down spout
may be needed to protect the heat pump.
Installation of Anchor Clamps
In Florida, building codes require that the heat pump be
anchored to the equipment pad or platform to withstand
high wind pressures created during hurricanes. Other
jurisdictions may have similar requirements. Please
check your local codes for further details.
This heat pump is provided with anchor clamps
designed to hold the unit to the equipment pad in high
wind conditions. Installation of the anchor clamps is
recommended in all installations and are required in
Florida (reference Florida Building Code, Mechanical
Section 301.13).
ENGLISH
E
F
7"
39"
15"
43"
15"
43"
F
Recommended Clearances
Operation
for Serviceability
Centimeters
Inches
60
36
30
24
30
24
30
24
150
60
Page 7
Centimeters
90
60
60
60
150