Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

9. Control Panel
Time
Change Password
Audible Alarm
Factory Reset
EEPROM Reset
EPO Function
Save Setting

9.3.6.2 System

The SETUP – SYSTEM screen may be accessed in any UPS operating mode. Some settings may only be amended in certain modes; refer to table
9.4 for details.
SYSTEM
Battery Mode Delay Time*
System Shutdown Time*
System Restore Time*
SmartOnline SV-Series UPS Operating Mode
Standby
Bypass
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Set output voltage: 120/127V (Default: 120V)
Output Voltage
Voltage – Upper limit: +10/15%; Lower limit: -10/20% (Default: +15/-20%)
Bypass Setting
Frequency – Upper limit: +1/2/4Hz; Lower limit: -1/2/4Hz (Default: +/- 4 Hz)
Set "Disable" or "Enable" (Default: Disabled)
Converter Mode
Set "Disable" or "Enable" (Default: Disabled)
ECO Mode
Set "Disable" or "Enable" (Default: Enabled)
Bypass Mode
Set "Disable" or "Enable" (Default: Enabled)
Auto Restart
Set "Disable" or "Enable" (Default: Disabled)
Cold Start
Refer to 7.3 Cold Start for more information
Set system shutdown delay time in battery mode (0-9990 sec.)
Set system shutdown time 0.2 – 99 min. (Default: 0.2 min.)
Set system restore time 0-9999 min. (Default: 001)
Total Power - Quantity of Power Modules installed
Redundancy*
Redundancy - Quantity of Power Modules to be redundant
Set "Disable" or "Enable" (Default: Disabled)
Charger Test
When this feature is enabled and the battery breaker of the UPS system is on, LCD can
display the charger voltage
Line
Battery
Battery Test
Y
Y
Y
Y
Y
Y
Table 9.3
24
Fault
Converter
Y
Y
Y
Y
Y
Y
ECO
Y
Y
Y
Y
Y
Y

Publicidad

Tabla de contenido

Solución de problemas

loading

Este manual también es adecuado para:

Smartonline 208v sv 20kSmartonline 208v sv 40kSmartonline 208v sv 60kSmartonline 208v sv 80kSmartonline 208v sv 100kSmartonline 208v sv 120k ... Mostrar todo

Tabla de contenido