Spacer holder
It is recommended that shut-off valves are fitted before and after the
energy meter to simplify removing the meter.
The meter should be installed in a conveniently accessible position for
service and operating personnel.
Initial operation is to be carried out and recorded after installation.
4.
Temperature sensor
Disconnectable temperature sensors or temperature sensors not
secured with their own calibration sticker must have their own
EU approval and CE label.
Handle the temperature sensor carefully!
The sensor cables are provided with coloured type plates:
Red: Sensor in the hot line
Blue: Sensor in the cold line
The maximum cable length of the temperature sensors is 6 m for the
PT100 and 10 m for the PT500.
The connecting cables must not be shortened or extended.
The free temperature sensors can be fitted so they are directly sub-
merged (e.g. ball valve) or in a pocket tested for conformity for this
sensor type.
Sensors must be installed symmetrically.
After initial operation of the meter, ensure that the temperature sen-
sors are always correctly connected at the calculator.