1.
Test the detector at the point of time you feel the lamp needs to
be switched on.
2.
Turn the LUX knob fully clockwise; turn the TIME knob fully anti-
clockwise.
3.
Switch on the power. The detector needs a warm-up time of
± 30 seconds before it will switch on the connected lamp. When
no signal is detected, the lamp will switch off after
± 10 seconds.
4.
Turn the LUX knob fully anti-clockwise. The lamp should switch
off.
5.5
Setting the Detector
1.
Turn the LUX knob until the lamp switches on.
2.
Now, set the switch-off delay with the TIME knob going from
± 10 seconds to ± 7 minutes.
3.
Close the detector with the cover and tighten the screw.
6.
Cleaning and Maintenance
The detector does not need any particular maintenance. However,
occasionally wipe it with a damp cloth to keep it looking new. Do not
use harsh chemicals, cleaning solvents or strong detergents.
7.
Technical Specifications
power supply
detection range
detection angle
light control
activation duration
installation height
power consumption
motion speed detection
working temperature
working humidity
max. rated load
resistive
inductive
V. 01 – 12/06/2015
PIR700
220-240 VAC, 50 Hz
12 m
180°
3 to 2000 lux (adjustable)
min. 10 s ± 3 s to max. 7 min ± 2 min
1.8-2.5 m
0.5 W
0.6-1.5 m/s
-20° C to +40° C
< 93 % RH
1200 W
300 W
5