VS FloPro™ Variable-Speed Pumps
®
ELECTRICAL SHOCK HAZARD
Turn off all switches and the main breaker in the variable-
speed pump electrical circuit, and allow five (5) minutes,
before starting the procedure. Failure to comply may cause
a shock hazard resulting in severe personal injury or death.
2.
Remove the cover of the junction box and feed the
RS-485 cable into the fitting.
3.
Unplug the RS-485 connector.
4.
Attach the four (4) wires in the RS-485 cable to
the RS-485 connector. Match the wire colors with
the positions on the connector: 1- red, 2- black, 3-
yellow, and 4- green. See Figure 9.
5.
Insert the RS-485 connector back into the pump.
6.
Slide DIP switches 1 and 2 up, so they are in the
ON position, and slide switches 3 and 4 down, so
they are in the OFF position. See Figure 9.
Controller
(Rear View)
5-Position
DIP Switch
Figure 9.
Wiring Variable-Speed Controller (JEP-R)
|
Installation & Operation Manual
WARNING
5 4 3 2 1
4 3 2 1
RS485
REMOTE CONTROL
Variable-Speed
Pump
Power Wiring
Port
Product may differ from images shown
ENGLISH
7.
Connect the other end of the cable to the controller.
Match the colors of the wires with the appropriate
connector positions as follows: 1- red, 2- black, 3-
yellow, and 4- green.
8.
Secure wiring access cover to the pump motor.
9.
Restore power to the pump and verify the operation
of the controller.
10. Refer to the Variable-Speed Controller Owner's
Manual, H0412200, to operate the pump.
Remove to
access
DIP switch
Figure 10. DIP Switch Access Cover
3.3
VS FloPro Pump DIP Switch Settings
The 5-position DIP switch is located at the rear of the VS
FloPro pump. This DIP switch serves two (2) functions:
it selects the pump address, and it determines what type
of controller will be used with the pump.
Table 4.
5-Position DIP Switch Settings
Switch
Switch
Switch
1
2
5
OFF
OFF
ON
ON
ON
ON
Switch
Switch
Pump Address
3
4
OFF
OFF
PUMP 1
ON
OFF
PUMP 2
OFF
ON
PUMP 3
ON
ON
PUMP 4
Page 13
Controller
AquaLink RS, AquaLink
PDA, or AquaLink Z4™
JEP-R and iQPUMP01