Foreman Ductable Dual Fuel Indirect-Fired Heater

Duct Installation

This heater may be ducted using the approved L.B.
White distribution devices:
-- (2) 12 in./30.48 cm Dia. x 25 ft. / 7.62 m duct
kit, L.B. White Part # 30052, duct adapter not
required.
-- Substitute ductwork material is acceptable but
must conform to the following requirements:
1. Duct must have a minimum material temperature
of 300°F/149°C
2. Duct length not to exceed 25 ft. /7.62 m per duct.
-- Locate the duct under suitable wind barrier materi-
als for jobsite requirements.
3. Alternate 12" duct can be used from the following
manufacturer's:
- Artic Helix - Norseman
- Artic Econorush - Norseman
- Hitex Series - NTI Global
- Ventflex Series - NTI Global
NOTE:
■ When using the ducting, ensure that bends in
ducts are kept to a minimum. A maximum of two
90° bends is allowed.
■ Reducing the number of bends will ensure that the
warm air exiting the heater flows freely, thereby
preventing overheating. If there are excessive
bends, the high limit switches may open.
Owner's Manual • Foreman
13