LERBAKKEN 10, 8410 RØNDE DENMARK
9202
For safe installation of 9202B the following must be observed. The module shall only be
installed by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
4501
For Installation in Zone 2 / Division 2 the following must be observed.
The 4501 programming module is to be used solely with PR electronics modules. It is
important that the module is undamaged and has not been altered or modified in any way.
Only 4501 modules free of dust and moisture shall be installed.
IECEx Certificate
Marking
Standards
Hazardous area
Zone 0, 1, 2, 20, 21, 22
CH1 (terminal 41,42,43,44)
CH2 (terminal 51,52,53,54)
U
:10.6 VDC
o
I
: 12 mADC
o
P
: 32 mW
o
Lo/Ro:1150 µH/Ω
IIC
IIB
2.0 µF
6.0 µF
C
o.
L
260 mH 780 mH 1000 mH
o.
Revision date:
2008-08-11
IECEx Installation drawing
KEM 06.0039 X
Ex nA nC IIC/IIB/IIA T4
[Zone 0] [Ex ia] IIC/IIB/IIA
[Zone 20] [Ex iaD]
IEC60079-15 :2005, IEC60079-11:2006, IEC60079-0: 2004
IEC60079-26: 2006, IEC61241-0: 2004, IEC61241-11:2005
Non Hazardous area
or Zone 2
-20 Ta 60ºC
+
44
43
CH1
-
42
41
+
54
53
CH2
-
52
51
IIA
18 µF
Version Revision
V3 R2
4501
34
33
32
31
14
13
12
11
9202
91 92 93 94 95
Power
Rail
Prepared by:
9202QI01
Supply / Output
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
U
: 253 V, max. 400 Hz
m
PB
Page:
21