For safe installation of 9202B the following must be observed. The module shall only be
installed by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
4501
For Installation in Zone 2 / Division 2 the following must be observed.
The 4501 programming module is to be used solely with PR electronics modules. It is
important that the module is undamaged and has not been altered or modified in any way.
Only 4501 modules free of dust and moisture shall be installed.
ATEX Certificate
Marking
Standards
Hazardous area
Zone 0,1, 2, 20, 21, 22
Ex input
CH1 (terminal 41,42,43,44)
CH2 (terminal 51,52,53,54)
U
:10.6 VDC
o
I
: 12 mADC
o
P
: 32 mW
o
Lo/Ro:1150 µH/Ω
IIC
IIB
2.0 µF
6.0 µF
C
o.
L
260 mH
780 mH
o.
Revision date:
2008-08-11

ATEX Installation drawing

KEMA 07 ATEX 0146 X
II 3 G Ex nA nC IIC/IIB/IIA T4
II (1) G [Ex ia] IIC/IIB/IIA
II (1) D [Ex iaD]
EN 60079-0 : 2004, EN 60079-11 : 2007, EN 60079-15 : 2005
EN 60079-26 : 2004, EN 61241-0 : 2006, EN 61241-11 : 2006
EN 50014 : 1997 + A1 + A2, EN 50020 : 2002, EN 50284 : 1999
EN 50281-1-1 : 1998
Non Hazardous area
or Zone 2
-20 ” Ta ” 60ºC
+
44
43
CH1
-
42
41
+
54
53
CH2
-
52
51
IIA
18 µF
1000 mH
Version Revision
V3 R2
4501
34
33
32
31
14
13
12
11
9202
91 92 93 94 95
Power
Rail
Prepared by:
9202QA01
Supply / Output
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
U
: 253 V max. 400 Hz
m
PB
Page:

23

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

9202b

Tabla de contenido