ICON / COLOR
STEADY ICON
/ RED
- Alarm ON
/ GREEN
- Mode: HEATING
/ GREEN
- Mode: COOLING
/ GREEN
- Mode: STAND-BY
/ GREEN
/
/ GREEN
- Configurable
- Current HR
/ RED
- Time slots activ.
/ RED
/
/ RED
/
/ RED
Not used
/ RED
Menu surf
LED N°*
DESCRIPTION
First capacity step
1
3
Primary circuit pump
5
Electrical heater
6
Sanitary hot water valve / pump
7
Boiler

6.3 Folder structure

Folder structure is composed of totally four menus
1) Main display → used to set what to display without acting on any
key
Ai → analogue input (temperature, pressure)
rtC → room time clock
SetP → standard set-point
SetR → corrected set-point (according to climatic correction,
etc.)
2) Operating mode → used to set operating mode
StbY → stand-by
HEAT → heating
COOL → cooling
AS → sanitary hot water
3) Status → used to show resources values
Ai (AIL/AIE/Air) → analogue inputs (main board / expansion
board / remote terminal)
di (diL/diE) → digital inputs (main board / expansion board)
AO (AOL/AOE) → analogue outputs (main board/expansion
board)
CL (HOUr/dAtE/YEAr) → clock
AL (Er00 → Er98) → alarms
SP → standard set-point
Sr → corrected set-point (according to climatic correction,
etc.)
4) Program → define parameters, functions, password and to display
alarm log
6 - Control (continued)
BLINKING ICON
- Alarm QUIT
- Antifreeze+Heat pump ON
- Heating mode by remote
- Cooling mode by remote
- Stand-by mode by remote
/
- Configurable
- HR setting
- Time slots programming
/
/
Not used
/
ICON

6.4 Menu structure

"Program" menu is composed of totally four folders
1) Parameters → change unit parameters
2) Functions → manual operations (switch ON / switch OFF, alarm
quit, historic alarm delete, multi function key use)
3) Password → define visibility levels for parameters/folders
4) Alarm log → display alarm log
Parameter folder gives access to following sub-folders
CL/CE/Cr/CF → configure device I/O (L → local; E → expansion; r
→ remote; F → serial)
• analogue inputs (type of probe, range, differential, logic
function)
• digital inputs (logic function)
• digital outputs (logic function)
• analogue outputs (range)
• serial configuration (communication parameters)
TR → define thermoregulation parameters
• set-point (max/min/hysteresis)
• type (proportional/differential)
• probe selection
ST → define operating status
• cooling only
• heating only
• scooling and heating
• change-over
CP → configure compressor parameters (type/number/timing)
PI → define primary circuit / source side circuit pump parameters
/ functions
• operating mode (disable / always ON / ON if compressor ON)
• digital / analogue control
• anti-sticking
• anti-freeze
BR → control the parameters for an additional step for heating
and for sanitary hot water integration (boiler)
• operating mode (disable / differential → fixed or in function of
outdoor air temperature)
• set-point / hysteresis
DS → define set-point offset (dynamic set-point) depending on
• analogue input (0...1V, 0...5V, 0...10V, 4...20mA)
• outdoor air temperature
• room temperature
AD → simulate an electronic inertial accumulator, acting on set-
point and hysteresis (adaptive function), by confronting minimum
/ effective ON-OFF time
AS → define sanitary hot water management parameters
• operating mode (disable / sanitary hot water valve / resistance
/ pump)
• set-point / hysteresis
• anti-legionella function
HP → define heat pump block management parameters
• outdoor air temperature
• thermoregulation temperature
• digital input
PL → define capacity limitation to protect the unit (high/low T,
high/low P)
TE → define time slots management (different operating daily
profiles)
AL → define alarms management (automatic / manual reset, by-
pass time, sampling)